Huawei RMS-SNMP01A User Manual page 42

Snmp card
Hide thumbs Also See for RMS-SNMP01A:
Table of Contents

Advertisement

RMS-SNMP01A SNMP Card
User Manual
Figure 4-14 Control page
Table 4-4 Definition of battery tests
Test Name
Shallow discharge test
Capacity test
You can perform the following operations on the Control page:
Issue 08 (2020-01-09)
Figure 4-14
uses the UPS2000-G as an example. The UPS2000-A does not provide battery management
functions. Only startup and shutdown operations can be performed on the UPS2000-A.
When the shallow discharge test conditions are met, click Start to perform a shallow
discharge test.
When the capacity test conditions are met, click Start to perform a capacity test.
After a capacity test or shallow discharge test starts, click Stop to stop the test.
When batteries are in the float charging state, click Manual equalized charging to start
equalized charging.
When batteries are in the equalized charging state, click Manual float charging to start
float charging.
Copyright © Huawei Technologies Co., Ltd.
4 Managing the UPS on the WebUI
Definition
A manual shallow discharge test designed to
test the short-time backup capacity after
long-time (60 days by default) battery
charging.
A manual deep discharge test designed to
obtain the battery discharge performance
data.
34