Huawei RMS-SNMP01A User Manual page 47

Snmp card
Hide thumbs Also See for RMS-SNMP01A:
Table of Contents

Advertisement

RMS-SNMP01A SNMP Card
User Manual
If the UPS monitor does not support the DHCP function, after the DHCP is selected for the
SNMP card, you cannot set the IP address of the SNMP card on the UPS monitor. You are
advised to update the version of the UPS monitor.
On the WebUI, the MAC address of the SNMP card is displayed. You can select DHCP and
click Submit to apply for a dynamic IP address to the DHCP server. After that, log in to the
WebUI using the newly applied IP address. If you select When the IP address is
automatically assigned, send an email., the SNMP card will send an email to you to notify
the IP address change.
The NAT uses a few public IP addresses to represent a large number of private IP addresses so
that the SNMP card in the internal network can be accessed through the external network.
This function is disabled by default. If this function is enabled, you can access the SNMP card
in the internal network through the external network by using a router with the NAT function.
Issue 08 (2020-01-09)
You are advised to select When the IP address is automatically assigned, send an email.
If DHCP fails to be allocated, the IP address of the SNMP card will restore to the default IP address
192.168.0.10 and the DHCP will be deselected.
If DHCP is selected and the IP address expires during SNMP card power-off, the IP address will be
reallocated after the SNMP card starts.
If DHCP is selected and DHCP fails to be allocated after the SNMP card restarts, the IP address of
the SNMP card will restore to the default IP address 192.168.0.10.