Setting And Adjusting Setpoints - Siemens RDG100KN Basic Documentation

With knx communications
Hide thumbs Also See for RDG100KN:
Table of Contents

Advertisement

K N X
R
Comfort basic setpoint
Comfort setpoint
Economy heating
4)
setpoint
Economy cooling
4)
setpoint
Commissioning
– HMI
– Tool download
Comfort basic setpoint
1)
dead zone Comfort
Setpoint Economy Heating
Setpoint Economy Cooling
Setpoint Protection Heating
Setpoint Protection Cooling
Current runtime
setpoints in
thermostat
Comfort setpoint
Economy Heating
Economy Cooling
Protection Heating
Protection Cooling
Actual room operating mode
K N X
R
Current setpoint
26 / 132
Siemens
Building Technologies
3.3.2

Setting and adjusting setpoints

Room temperature setpoints can be...
– set during commissioning
– adjusted during runtime
The source can be one of the followings:
– The local HMI
– A tool
– A central control unit
The thermostat stores the setpoints in...
– EEPROM in the form of parameters
– The runtime memory
The table below shows the interrelations:
Setpoint setting
Input LTE-Mode
Setpoints Heating
Setpoints Cooling
Setpoints Heating
Setpoints Cooling
Setpoint
adjustment
Input
Input S-Mode
2)
LTE-Mode
Setpoint shift H
Comfort setpoint
Setpoint shift C
Setpoint shift H
Setpoint shift C
Current setpoint (used by the thermostat for temperature control)
1)
Only required for heating and cooling applications (see 3.6.12)
2)
LTE-Mode: Shift is added to the local shift
3)
S-Mode: The last option selected is always used, either S-Mode input or local operation
4)
To display the S-Mode objects of the Economy heating and cooling setpoint (P11/P12), set the
control parameter "Room temperature: Economy setpoints" to as group object in ETS tool
The current setpoint (used by the thermostat for temperature control) is available
on the bus for use in the central control unit.
RDG100KN, RDG160KN, RDG165KN Basic Documentation
Input S-Mode
Comfort basic
setpoint
Setpoints Heating
Setpoints Cooling
3)
Local
operation
Rotary knob
Stored in the EEPROM
of thermostat
P08 Comfort basic setpoint
P33 Dead zone Comfort
P11 Economy Heating
P12 Economy Cooling
P65 Protection Heating
P66 Protection Cooling
New current
runtime setpoints
in thermostat
3)
Comfort setpoint
Economy Heating
Economy Cooling
Protection Heating
Protection Cooling
CE1P3191en
2018-07-03
1)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdg160knRdg165kn