Siemens RDG100KN Basic Documentation page 23

With knx communications
Hide thumbs Also See for RDG100KN:
Table of Contents

Advertisement

Example 3 (RDG16..KN)
Time schedule
Room operating
mode
Presence
detector
Window contact
Room 3
Actual room
operating mode
Room 3
Siemens
Building Technologies
Application for "Window Contact", "Presence Detector" and "Central time
schedule"
In room 3, the time schedule set available between 13:00 and 17:00.
·
In the morning, as soon as the presence is detected, the operating mode
switches to Comfort (1)
·
The users open the window for a short time and the operating mode switches
to Protection (2)
·
In the afternoon, the central time schedule sets the Comfort mode from 13:00
to 17:00 (3)
·
After 17:00, the room is still occupied and the operating mode remains in
Comfort (occupancy via presence detector) (4)
·
The users open the window and exit the room for a short time. The operating
mode switches to Protection as long as the window is open (5)
·
As soon as the room is unoccupied, the thermostat switches to Economy (6)
·
After this time period, the occupancy detected by presence detector has no
effect, and the central time schedule sets the thermostat to Protection (7)
Comfort
Pre-Comfort
Economy
Protection
(holidays or
special days)
Occupied
Unoccupied
Window open
Window closed
Comfort
Economy
Protection
RDG100KN, RDG160KN, RDG165KN Basic Documentation
23 / 132
CE1P3191en
2018-07-03