Wall-mounted room thermostats with lcd
Hide thumbs Also See for RDG1 Series:

Advertisement

Quick Links

s
RDG100
RDG110
RDG110U
CE1N3181en
2017-11-20
RDG100T
RDG160T
RDG160TU
Wall-mounted room
thermostats with LCD
for fan coil unit applications
for universal applications
for use with compressors in DX-type equipment
∂ RDG100..: Operating voltage AC 230 V, On/Off, 3-positon or PWM control
outputs
∂ RDG110: Operating voltage AC 230 V, On/Off relay (SPDT) outputs
∂ RDG110U: Operating voltage AC/DC 24 V, On/Off relay (SPDT) outputs
∂ RDG100../RDG110..: Output for 1-speed and 3-speed
∂ RDG160T..: Operating voltage AC/DC 24 V, DC 0...10 V or On/Off control
outputs
∂ RDG160T..: Output for 1-speed, 3-speed or ECM fan DC 0...10 V
∂ Operating modes: Comfort, Economy and Protection
∂ Automatic or manual fan speed
∂ 3 multifunctional inputs for keycard contact, external sensor, etc
∂ Automatic or manual heating/cooling changeover
∂ Adjustable commissioning and control parameters
∂ Minimum and maximum setpoint limitation
∂ Backlit display
Additional features of RDG100T, RDG160T.., RDG100T/H:
∂ Infrared remote control receiver
∂ Auto Timer mode with 8 programmable timers
∂ Auto timer can be disabled via P02
∂ Auto timer can be disabled via DIP switches (RDG160T..)
∂ Landscape design (RDG100T/H only)
∂ Selectable relay output functions (RDG160T..)
RDG100T/H
Building Technologies
3
181
RDG1..

Advertisement

loading

Summary of Contents for Siemens RDG1 Series

  • Page 1 RDG100 RDG100T RDG100T/H RDG110 RDG160T RDG110U RDG160TU Wall-mounted room RDG1.. thermostats with LCD for fan coil unit applications for universal applications for use with compressors in DX-type equipment ∂ RDG100..: Operating voltage AC 230 V, On/Off, 3-positon or PWM control outputs ∂...
  • Page 2 ∂ 1-stage compressor for heating or cooling and radiator/floor heating ∂ 1-stage compressor for heating and cooling ∂ 1-stage compressor for heating and cooling with reversing valve ∂ 2-stage compressor for heating or cooling 2/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 3 For switching OFF external equipment OFF during Protection mode For switching ON external equipment (such as. pump) during H/C demand Output heating/cooling sequence ∂ Wizard function to select working temperature unit °C or °F (RDG160TU, RDG110U) 3/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 4 Product no. Control outputs RDG100.. On/Off, PWM, 3-position 3-speed, 1-speed RDG110/RDG110U On/Off (SPDT) 3-speed, 1-speed DC 0...10 V 3-speed, 1-speed RDG160T/RDG160TU On/Off, DC 0...10 V DC 0...10 V ECM 4/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 5 ∂ Chilled ceiling heated ceiling and radiator YHC1 YHC2 Using Using RDG100../RDG110../RDG160T.. RDG100../RDG110../RDG160T.. Product no. Control outputs RDG100.. On/Off, PWM, 3-position RDG110/RDG110U On/Off (SPDT) RDG160T/RDG160TU On/Off, DC 0...10 V 5/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 6 Heating/cooling valve actuator 1-speed or 3-speed fan Heating valve actuator Return air temperature sensor or external room Cooling valve actuator temperature sensor (optional) Electric heater Changeover sensor (optional) 6/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 7 (only available in AP, UAE, SA and IN) On/Off and PWM Thermal actuator (for radiator valves) 4884 STA23.. actuators AC 230 V, NO Thermal actuator (for radiator valves) 4884 STA73.. AC 24 V, NO 7/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 8 Maximum number of actuators in parallel on the RDG160T..: ∂ 10 SS..61.. actuators (DC) ∂ 10 ST..23/63/73.. actuators (DC or On/Off) ∂ 10 SFA.., SUA.., MVI.., MXI.. On/Off actuators ∂ 10 SQS65.. actuators (DC) 8/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 9 RDG100T/H RDG110 RDG160T RDG110U RDG160TU Operating mode selector/Esc Button to enter the time and to set the timers Fan mode selector/OK Rotary knob for setpoint and parameter adjustment 9/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 10 Temporary timer function (visible when Afternoon: 12-hour format operating mode is temporarily extended due to prolonged presence or absence) Confirmation of parameters Indicates that room temperature is displayed 10/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 11 ∂ Selectable relay function (RDG160T..). Consider overall maximum current though the relays. ∂ Disconnect power supply before removing the thermostat from the mounting plate! 11/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 12 European Directive 2012/19/EU and may not be disposed of as domestic garbage. ∂ Dispose of the device through channels provided for this purpose. ∂ Comply with all local and currently applicable laws and regulations. 12/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 13 PWM (TPI) room thermostat, for use with Class IV value 2.0% On/Off output heaters RDG110 Application with On / Off operation of a heater Class I value 1.0% 13/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 14 Do not mix with X1/X2! Function input External temperature sensor, changeover sensor, Selectable operating mode switchover contact, dewpoint monitor contact, enable electric heater contact, fault contact 14/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 15 External room temperature sensor, heating/cooling X1: P38 changeover sensor, operating mode switchover X2: P40 contact, dewpoint monitor contact, enable electric D1: P42 heater contact, fault contact, monitoring input, supply air temperature 15/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 16 CE1T3181en_C1 RCM Conformity UL 916 PAZX CSA-C22.2 No. 205 PAZX7 http://database.ul.com UL (RDG110U/RDG160TU) Safety class RDG160T II as per EN60730 RDG160TU III as per EN60730 Pollution class Normal 16/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 17: Environmental Compatibility

    L, N, Q1, Q2, Q3, Y1, Y2, Y3, Y4, Y11, Y21 Housing front color RAL 9003 white Weight RDG100../RDG110.. 0.30 kg RDG160T.. 0.32 kg The documents can be downloaded from http://siemens.com/bt/download. Connection terminals L, N Operating voltage AC 230 V RDG100, G, G0 Operating voltage AC/DC 24 V RDG100T, Note: For DC 24 V: G0 = –;...
  • Page 18 Heating valve actuator Cooling valve actuator ∂ 2-pipe & el. heater Heating/cooling valve actuator Radiator valve actuator Electric heater with relay/contactor ∂ 4-pipe & el. heater YHC1/YHC2 stage 18/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 19 Radiator valve actuator Electric heater max. 5 A ∂ Compressor & el. YHC1/YHC2 stage heater C1/C2 Compressor 1 and 2 stage Reversing valve ∂ Compressor & reversing valve 19/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 20 ∂ Compressor & reversing valve For US installations, use Class 2 rated power supplies. For other installations, use circuit breakers with rated current of no more than 10 A. 20/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 21 Heating valve actuator external room temperature, changeover sensor, Cooling valve actuator etc.) Heating/cooling valve actuator Electric heater max. 5 A YHC1/YHC2 stage C1, C2 Compressor 1 stage Radiator valve actuator 21/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 22 Electric heater max. 5 A YHC1/YHC2 stage For US installations, use Class 2 rated power supplies. For other installations, use circuit breakers with rated current of no more than 10 A. 22/23 Siemens RDG1... Wall-mounted room thermostats with LCD CE1N3181en Building Technologies 2017-11-20...
  • Page 23 28.3 28.3 (0.63’’) (0.35’’) (1.11’’) (1.11’’) Issued by © Siemens Switzerland Ltd, 2016 - 2017 Siemens Switzerland Ltd. Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6300 Zug Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies...