Setting And Adjusting Setpoints - Siemens RDG400KN Basic Documentation

Room thermostat with knx communications
Hide thumbs Also See for RDG400KN:
Table of Contents

Advertisement

Caution
K N X
R
Comfort basic setpoint
Comfort setpoint
Commissioning
– HMI
– Tool download
Comfort basic setpoint
Dead zone Comfort 1)
Setpoint Economy Heating
Setpoint Economy Cooling
Setpoint Protection Heating
Setpoint Protection Cooling
Current runtime
setpoints in
thermostat
Comfort setpoint
Economy Heating
Economy Cooling
Protection Heating
Protection Cooling
Effective room operating mode
22 / 78
Siemens
Building Technologies
If a setpoint (Economy or Protection) is set to OFF, the thermostat does not control
the room temperature in the corresponding mode (heating or cooling).
This means no protective heating or cooling function and thus risk of frost in
heating mode or risk of overtemperature in cooling mode!
The Economy setpoints are accessible at the service level (P11, P12); the
Protection setpoints at the expert level (P65, P66).
3.3.2

Setting and adjusting setpoints

Room temperature setpoints can be
– set during commissioning
– adjusted during runtime
The source can be
– the local HMI
– a tool
– a central control unit
The thermostat stores the setpoints
– in EEPROM in the form of parameters
– in the runtime memory
The table below shows the interrelations:
Setpoint setting
Input LTE mode
Setpoints Heating
Setpoints Cooling
Setpoints Heating
Setpoints Cooling
Setpoint
adjustment
Input LTE mode
Input S-mode
2)
3)
Setpoint shift H
Comfort setpoint
Setpoint shift C
Setpoint shift H
Setpoint shift C
Current setpoint (used by the thermostat for temperature control)
RDG400KN Basic documentation
Functions
Input S-mode
Comfort basic setpoint
Local ope-
ration 3)
Rotary knob
Stored in EEPROM
of thermostat
P08 Comfort basic setpoint
P33 Dead zone Comfort 1)
P11 Economy Heating
P12 Economy Cooling
P65 Protection Heating
P66 Protection Cooling
New current
runtime setpoints
in thermostat
Comfort setpoint
Economy Heating
Economy Cooling
Protection Heating
Protection Cooling
CE1P3192en
20 Jul 2010