Operating Instructions en
RDG100KN / RDG160KN – the room thermostat with KNX communications that allows you to set the
ideal room temperature you want. The thermostat provides Comfort, Economy and Protection mode.
In addition it can operate in Auto timer mode according to a schedule via KNX bus.
The fan operates either in Automatic mode or at the selected speed when using Manual mode.
You can either rely on the factory settings or make adjustments that suit your individual needs.
Main display
Room temperature in degrees
Celsius
Room temperature in degrees
Fahrenheit
Button lock active
Fault indicator *
Condensation in the room *
Timer function active
Weekday 1 = Monday
Additional user info, e.g.
current time of day
Escape (Cancel)
Confirm (OK)
Operating mode button
Fan mode button
Rotary knob
* Needs to be configured by your HVAC installer
Changing the room temperature
Turn the rotary knob clockwise (+) to increase, or counterclockwise (-) to decrease
the current room temperature setpoint. The thermostat changes to Comfort
The setting range is from 5...40 °C; it can be limited by parameters P09 and P10.
(for parameter settings, see reverse side).
Adjusting the fan speed
Press the right button repeatedly until the desired fan mode is reached.
In Automatic mode
depending on the setpoint and the actual room temperature.
RDG100KN: When the room temperature reaches the setpoint, the fan keeps
running at low speed (factory setting).
RDG160KN: The fan stops (factory setting) or keeps running at low speed (P15).
In Manual mode, the fan operates independently and always runs at the speed
you set: low / medium / high.
Note:
Low Medium High
If desired, you can change the fan mode selector option via P03: Auto / manual, Manual only, or
Manual including Protection mode.
Changing the operating mode of the thermostat
Press the operating mode button repeatedly until the
mode you desire.
1. Protection mode
In protection mode, the plant stops operating. However, if the room temperature
falls below 8 °C, heating is switched on to protect the room against frost.
The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer: 
2. Comfort mode
In Comfort mode, the thermostat maintains the room temperature on the setpoint
which can be adjusted with the rotary knob
3. Auto Timer mode
In Auto Timer mode, the thermostat automatically switches over between Comfort
and Economy mode according to the schedule via KNX bus.
If no schedule via KNX is available, then Auto Timer is replaced by Comfort.
4. Economy mode
In Economy mode, the thermostat maintains the room temperature at a lower or
higher setpoint, thus saving energy and money.
The thermostat can be set to Economy mode either by pressing the operating
mode button if enabled (P02 = 2), or via an external signal (switch or KNX bus
command) such as window switch, keycard or presence detector.
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling.
They can be adjusted via parameters P11 and P12 (for parameter settings, see
reverse side).
Important: These setpoints can be set to OFF; which means that the thermostat
is not active., i.e. no protective heating or cooling function. Risk of frost!
Changing from heating to cooling mode
The changeover from heating to cooling (or vice versa) is made
– either automatically by a changeover sensor, or a changeover switch, or a
remote changeover switch via KNX command
– or manually by pressing the operating mode button.
If the thermostat is configured for "heating only" or "Cooling only", changeover is
not available (see parameter P01)
To select cooling or heating manually (P01=2), press the operating mode button
until the
symbol points to the mode you desire.
With automatic changeover or continuous heating / cooling, symbols
indicate that the system currently heats or cools.
With manual changeover, symbols
operates in heating or cooling mode. Symbols
currently heats or cools.
s
Operating mode
Room temperature
Heating mode
Electric heater active
Outdoor temperature
Cooling mode
Comfort mode
Economy mode
Auto timer mode
Protection mode:
Protection against frost
Indicator for mode selection
7 = Sunday
Fan mode
Automatic fan
Manual fan:
Low
Medium
High
, the fan speed is automatically selected by the thermostat
symbol points to the operating
Frost protection: _________ ˚C
Heat protection: __________˚C
indicate that the system currently
indicate that the system
RDG100KN
RDG160KN
.

Advertisement

loading

Summary of Contents for Siemens RDG100KN

  • Page 1 RDG100KN RDG160KN RDG100KN / RDG160KN – the room thermostat with KNX communications that allows you to set the ideal room temperature you want. The thermostat provides Comfort, Economy and Protection mode. In addition it can operate in Auto timer mode according to a schedule via KNX bus.
  • Page 2 When no time schedule via KNX exists, then Auto is equal to Comfort. *** Parameter P13 is only displayed with application 2-pipe with el. heater. All temperature settings can be made in increments of 0.5 °C.  Please record all changes you make! Siemens Building Technologies Subject to change CE1B3191en 2012-09-19...