Setting master / slave
44 / 132
Siemens
Building Technologies
User case A:
·
The user changes the operating mode and comfort setpoint on the master
thermostat. The data is transmitted to the slaves.
·
The user can modify the setpoint on slaves, if the button lock function (via
parameter P14) is not enabled. The master and slaves take over the new
setpoint.
·
The operating mode can be changed on an individual slave, but has no impact
on the other thermostats.
S-Mode binding:
S-Mode objects master
Setpoint:
[23]
Room temperature:
Comfort setpoint
Operation
[16]
Room operating mode: State
mode:
(out)
Application
[48]
Effective application
mode:
(out)
mode
Window
[20]
Room operating mode:
status
(in)
Window state
User case B:
·
The user changes the reference operating mode and comfort setpoint on all
thermostats (master and slave). The data is transmitted and updated on all
thermostats.
S-Mode objects master
Setpoint:
[23]
Room temperature:
Comfort setpoint
Operation
[7]
Room operating mode:
mode:
(out)
Preselection
Application
[48]
Effective application
mode:
(out)
mode
Window
[20]
Room operating mode:
status
(in)
Window state
The master and slave function must be selected on RDG160KN via ETS.
(SW version
2.04).
Object "[48] Effective application mode" is visible, if the thermostat operates as the
master (default setting).
RDG100KN, RDG160KN, RDG165KN Basic Documentation
S-Mode objects slave
[23]
Room temperature:
Comfort setpoint
Room operating mode:
[7]
Preselection
(in)
[31]
Application mode
(in)
Room operating mode:
[20]
Window state
(out)
S-Mode objects slave
[23]
Room temperature:
Comfort setpoint
Room operating mode:
[7]
Preselection
(in)
[31]
Application mode
(in)
Room operating mode:
[20]
Window state
(out)
CE1P3191en