Plant diagram in ACS
Plant type
2-pipe
2-pipe fan coil unit
– Control sequence: No impact (P01 = any)
– Fan operation: Enabled (P52 <> 0)
Chilled/heated ceiling
– Control sequence: Changeover
– Fan operation: Disabled
Siemens
Building Technologies
The ACS tool offers plant diagrams for easy monitoring and operation of the
thermostat.
To start this application, select Applications à Plant operation à Standard
diagram.
The ACS tool provides standard plant diagrams for RDG.. KNX room thermostats,
depending on the following configurations:
Application
Configuration
(P52 = 0)
RDG100KN, RDG160KN, RDG165KN Basic Documentation
Application
Configuration
Radiator
– Control sequence: Heating only (P01 = 0)
– Fan operation: Disabled
Chilled ceiling
– Control sequence: Cooling only
– Fan operation: Disabled
(P52 = 0)
(P52 = 0)