Example 2:
Dehumidifier,
DC fan + valve,
No shifting setpoint
Example 3:
Dehum./DC fan,
On/Off valves
Siemens
Building Technologies
2-pipe fan coil application for dehumidification, with DC fan and DC valve (without
temperature setpoint shifting):
Commissioning
·
Fan
P53 = 3 (or DIP4 = OFF)
·
Control strategy
P75 = 3 (factory setting)
·
Setpoint high
P21 = 50 % (factory setting
·
Temp. shift
P76 = 0
·
Valve
P46 = 2 (factory setting)
·
Relay function
P74 = 7 (dehumidifier)
8
See
for min. and max. ratings
4-pipe fan coil application for dehumidification, with temperature setpoint shifting,
dehumidifier contact, DC fan and On/Off valves:
Commissioning
·
Fan
P53 = 3 (or DIP4 = OFF)
·
Control strategy
P75 = 3 (factory setting)
·
Setpoint high
P21 = 50% (factory setting)
·
Temp. shift
P76 = 3 K (factory setting)
·
Valves
P46/47 = 1
·
Relay function
P74 = 7 (dehumidifier)
8
See
for min. and max. ratings.
RDG100KN, RDG160KN, RDG165KN Basic Documentation
Outputs used
·
M1
DC fan
·
V1
DC valve
·
*)
L3
Dehumidifier
*)
Release contact
Outputs used
·
M1
DC fan
·
V1, V2 On/Off valves
·
*)
L3
Dehumidifier
*)
Release contact
119 / 132
CE1P3191en
2018-07-03