Siemens RDG100KN Basic Documentation page 18

With knx communications
Hide thumbs Also See for RDG100KN:
Table of Contents

Advertisement

Operating mode
switchover contact
(RDG100KN)
Window contact
(RDG16..KN)
KNX
R
Room operating mode:
Window state
Notes
KNX
R
Presence detector
(RDG16..KN)
Notes
18 / 132
Siemens
Building Technologies
The thermostat is forced to Economy mode when ...
·
a window is open
·
a presence detector signals "no one present"
·
the keycard of a hotel room is withdrawn, etc.
The contact can be connected to digital input D1 or multifunctional input X1, X2.
Set P38, P40 or P42 to 3. P02 is not relevant. User operations are ineffective and
OFF displays if the operating mode switchover contact is active.
The thermostat is forced into Protection mode when the window is open. The
contact can be connected to multifunctional input X1, X2 or digital input D1. Set
P38, P40 or P42 to 3. User operations are ineffective and OFF displays if the
window contact is active.
The function operating mode switchover (window contact) is also available via the
KNX signal "Window state", e.g. from a KNX switch or a KNX presence detector.
·
Only one input source must be used, either local input X1/X2/D1or KNX bus.
User operations are ineffective and OFF displays if the operating mode
switchover (window contact) is active, or if "Window state" is sent via bus.
·
When RDG160KN is set as slave, the window state (as Transmit) is sent to
the master and the operating mode of all slaves will be changed accordingly,
as long as at least one window contact is open
The operating mode can be changed to Comfort or Economy mode based on the
room occupancy (room occupied or unoccupied, via presence detector or keycard).
Time schedule
Presence detector behavior
via bus
·
Comfort mode
Whenever the presence detector is activated or deactivated,
the operating mode remains in Comfort
·
Whenever the presence detector is activated, the operating
Economy mode
mode goes to Comfort
·
Whenever the presence detector is deactivated, the
operating mode goes to Economy (with auto mode)
·
Presence detector has no influence on the operating mode
Protection mode
·
Whenever the presence detector is activated, the operating
Not available
mode goes to Comfort
·
Whenever the presence detector is deactivated, the
operating mode goes to Economy
·
When the time-switch changes to Economy but the presence detector is still
active, the operating mode remains in Comfort mode until the presence
detector becomes inactive
·
The contact (e.g. a card reader) can be connected to multifunctional input X1,
X2 or digital input D1 (set P38, P40 or P42 to 10) or the occupancy is sent via
bus from a KNX presence detector (only one input source must be used,
either local input X1/X2/D1 or KNX bus)