6. Commissioning
0
2
4
6
8
E
1
TEMP.: 68°
2
1
D
2
F
#
% $
AUTO
J
I
5"
Installer level - #NETWORK Menu
Parameter
CASCADE
(2)
VM NETWORK
MASTER CONTROLER
(3)
(4)
SYSTEM NETWORK
(4)
FUNCT
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
(2) The parameter is only displayed if CASCADE is set to NO
(3) The parameter is only displayed if CASCADE is set to ON
(4) The parameter is only displayed if MASTER CONTROLER is set to ON
(5) The parameter is only displayed if FUNCT is set to PARALLEL
(6) The parameter is only displayed if MASTER CONTROLER is set to OFF
122
10
12
14
16
18
20
22
24
SUNDAY 11:45
<

!
:
STD
C002235-F-04
(1)
Adjustment range Description
ON / NO
ON: System in cascade
Specific menu: Enlist VMs in cascade
mode
¼See chapter: "Connecting VM
iSystem in cascade", page 124
ON / NO
Configure this control system as master
on the bus
Specific menu: Enlist generators or VMs
in cascade mode
¼See chapter: "Connecting VM
iSystem in cascade", page 124
Operation in cascade: Successive
TRADITIONAL
tripping of the various generators in the
cascade according to needs
Functioning in parallel cascade: If the
PARALLEL
outside temperature is lower than the
PARALLEL.CASC value, all generators
are started up at the same time
Flat solar collectors
Solar panel
Area (m
installation
8...10
12...15
16...20
12...15
18...23
24...30
16...20
24...30
6.7.4.

Configuring the network

1. Access the installer level: Press key - for around 5 seconds.
2. Select the menu #NETWORK.
Turn the rotary button to scroll through the menus or
4
modify a value.
Press the rotary button to access the selected menu
4
or confirm a value modification.
¼ For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 97
3. Set the following parameters:
AFC 18 - AFC 24 - AFC 30
2
) Number of
Flow rate
panels
(l/h)
2x2
750
2x3
670
2x4
450
3x2
850
3x3
800
3x4
650
4x2
1200
4x3
850
Factory setting Customer
setting
NO
ON
TRADITIONAL
09/07/2015 - 300026439-07
Flow rate
(l/min)
12,5
11,2
7,5
14,2
13,4
10,9
20,0
14,2