5.8.9.
Connecting two heating circuits with
pressure breaker
8
SCU
SCU
Connect a safety thermostat if the heating circuit is for
A
underfloor heating.
Remove the bridge.
4
Connect the wires from the safety thermostat to the
4
connector.
Connect the 3-way valve flow sensor (circuit B).
Z
Connect the heating pump (circuit B).
E
Connect the 3-way valve (circuit B).
R
Do not connect anything to the terminal block.
T
AFC 18 - AFC 24 - AFC 30