6. Commissioning
6.6

Reading out measured values

0
2
4
6
8
E
1
2
1
D
2
bar
F
#

% $
AUTO
J
I
STD
User level - #MEASURES Menu
Parameter
Description
Outside temperature
OUTSIDE TEMP.
Room temperature of circuit A
(1)
ROOMTEMP.A
(1)
Room temperature of circuit B
ROOMTEMP.B
Room temperature of circuit C
(1)
ROOMTEMP.C
Water temperature in the boiler
BOILER TEMP
Water pressure in the installation
PRESSURE
(1) The parameter is only displayed for the options, circuits or sensors actually connected.
(2) The parameter is only displayed if the function is activated (parameter ENERGY METER in the #CONFIGURATION} menu)
110
T001522-A
10
12
14
16
18
20
22
24
SUNDAY 11:45
<
!
:
C002219-D-04
6.5.5.

Finalizing work

1. Remove the measuring equipment.
2. Put the flue gas sampling plug back in place.
3. Refit the front panel.
4. Raise the temperature in the heating system to approximately
50°C.
5. Shut down the boiler.
6. After about 10 minutes, vent the air in the heating system.
7. Checking the hydraulic pressure. If necessary, top up the water
level in the heating system (recommended system pressure
between 1.5 and 1.8 bar (0.15 MPa and 0.18 MPa)).
8. Explain the operation of the installation, the boiler and the
regulator to the users.
9. Inform the user of the periodicity of maintenance work to be carried
out. Input the service date and the contact details of the installer.
¼ See chapter: "Customising maintenance", page 129.
10.Give all the instruction manuals to the user.
Commissioning of the boiler is now complete.
The various boiler parameters are preset in the factory.
These factory settings are suitable for the most common
heating systems. For other systems and situations, the
parameters can be modified.
The various values measured by the appliance are displayed in the
#MEASURES menu.
1. To access user level: Press the > key.
2. Select the menu #MEASURES.
Turn the rotary button to scroll through the menus.
4
Press the rotary button to access the selected menu.
4
¼ For a detailed explanation of menu browsing, refer to
the chapter: "Browsing in the menus", page 97.
AFC 18 - AFC 24 - AFC 30
Unit
°C
°C
°C
°C
°C
bar (MPa)
09/07/2015 - 300026439-07