Configuring A Dhw Tank With Two Sensors; Reading Out Measured Values; List Of Measured Values; Cu-Gh08 Control Unit Counters - DeDietrich AMC 15 Installation And Service Manual

Wall-hung gas condensing boilers
Table of Contents

Advertisement

9 Settings
Tab.69
button > Installation Setup > SCB-10 > DHW tank > Parameters, counters, signals > Parameters
Code
Display text
CP000
MaxZoneTFlowSetpoint
CP420
ZoneDhwHysterisis
CP700
DHW Cal Offset zone
9.5

Reading out measured values

Fig.91
Parameters, counters, signals
9.6

List of measured values

Tab.70
On >
> Installation Setup > CU-GH08 > Auto filling CH > Parameters, counters, signals > Counters
Code
Text display
AC016
Amount Autofillings
Tab.71
On >
> Installation Setup > CU-GH08 > Gas fired appliance > Parameters, counters, signals > Counters
Code
Text display
AC002
Service Burning hrs
AC003
Hours Op. Service
92
AMC
9.4.3
When a domestic hot water tank with two sensors is connected to the
boiler, the loading of the tank depends on the water temperature
measured by the two sensors:
Description
Maximum Flow Temperature setpoint zone
Trip differential for DHW production
Offset for calorifier sensor per zone
The control unit continually registers various values from the boiler and the
connected sensors. These values can be read on the control panel of the
boiler.
A
B
AD-3000936-01
9.6.1
Description
Filling counter, count the amount of
automatic filling loops
Description
Number of hours that the appliance has
been producing energy since last service
Number of hours since the previous
servicing of the appliance

Configuring a DHW tank with two sensors

Loading of the tank will start when the top sensor measures a
temperature below (desired setpoint + CP700 – CP420).
Loading of the tank will stop when the bottom sensor measures a
temperature above (desired setpoint + CP700).
1. Press the
button.
2. Select > Installation Setup.
3. Select the zone or device you want to read out.
4. Select Parameters, counters, signals > Counters or Signals to read
out a counter or signal.
5. If available, select Adv. Counters or Adv. Signals to read out counters
or signals at the advanced installer level.
A
Parameters
Counters
Signals
Adv. Parameters
Adv. Counters
Adv. Signals
B List of settings or values

CU-GH08 control unit counters

Range
7 °C – 100 °C
1 °C – 60 °C
0 °C – 30 °C
Range
0 - 65534
Range
0 Hours - 131068 Hours
0 Hours - 131068 Hours
7686707 - v.01 - 06092018