Configuring The Network - DeDietrich Innovens MCA 15 Installation And Service Manual

Wall-hung gas condensing boilers
Hide thumbs Also See for Innovens MCA 15:
Table of Contents

Advertisement

5. Start-up
0
2
4
6
8
E
1
TEMP.: 68°
2
1
D
2
#
F
% $
AUTO
J
I
5"
"Installer" level - #NETWORK menu
Parameter
CASCADE:
MASTER
(2)
CONTROLLER
(3)
SYSTEM NETWORK
(3)
FUNCT
(4)
PARALLEL CASC.
(2)
INTER STAGE TIMER
(5)
SLAVE NUMBER
3WW PLC
InOne SCENARIO
REMOVE DEVICE
(1) The menu is displayed only if the INSTALLATION parameter is set to EXTENDED
(2) The parameter is only displayed if CASCADE is set to YES
(3) The parameter is displayed only if MASTER CONTROLER is set to YES
(4) The parameter is only displayed if FUNCT is set to PARALLEL
(5) The parameter is displayed only if MASTER CONTROLER is set to OFF
88
10
12
14
16
18
20
22
24
SUNDAY 11:45
!

:
<
STD
C002235-F-04
(1)
Adjustment range Description
ON / NO
ON: System in cascade
ON / NO
Configure this control system as master
on the bus
Specific menu: Enlist generators or VMs
in cascade mode (See following
chapter: "Connecting appliances in
cascade")
Operation in cascade: Successive
CLASSIC
triggering of the various boilers in the
cascade according to requirements
Functioning in parallel cascade: If the
PARALLEL
outside temperature is lower than the
value PARALLEL.CASC, all of the
boilers are started up at the same time
-10 to 20 °C
Outside temperature triggering all stages
in parallel mode
1 to 30 min
Time delay for starting up or shutting
down generators.
2 to 10
Set the network address of the
secondary generator
Specific menu (Not used)
Specific menu: Configure the InOne
scenarios to be managed by the SCU
PCB (See following chapter:
"Configuring the scenarios")
Specific menu: see below
5.7.4.

Configuring the network

1. Access the "installer" level: Press key - for around 5 seconds.
2. Select the menu #NETWORK.
Turn the rotary button to scroll through the menus or
4
modify a value.
Press the rotary button to access the menu selected
4
or confirm a value modification.
¼ For a detailed explanation of menu browsing, refer
to the chapter: "Browsing in the menus", page 62
3. To set the following parameters:
MCA 15 - MCA 25 MCA 25/28 MI
Factory setting Customer setting
NO
ON
CLASSIC
10 °C
4 mn
2
29/04/2010 - 300022146-001-B