10.2.5 Activating high- and low-pressure switches

➙ Prerequisite: High- and low-pressure transmitters
must be installed.
• In the menu M
S
AIN
ETUP
row E
/
NABLE HIGH
LOW PRESSURE LIMIT PROTECTION
column U
S
SER
ETTING
• Adjusting cut-out pressures: In the rows H
S
: V
and L
SURE
WITCH
ALUE
enter the appropriate limits as absolute pressure in
the column U
S
SER
ETTING
1.2 bar, absolute pressure in each case. The high
pressure cannot be increased any further.

10.2.6 Configuring a spare part

When a CM-RC-01 has been replaced, the specific
compressor parameters must be set.
• Connect the PC/mobile device to the new CM-RC-01
via the BEST interface converter.
• Open the BEST SOFTWARE and select new CM-
RC-01.
• Perform firmware update.
• Select compressor from the suggestion list.
• In the menu C
ONFIGURATION
• Check all other parameters and adjust if necessary.

10.3 Data log

All monitored operating parameters and alarm mes-
sages are stored internally:
• All operating parameters in 5- or 10-second intervals
• Storage capacity: approx. 2 weeks in case of normal
operating behaviour
• Alarm messages and statistics of the last 365 days
This data can be exported using the BEST
SOFTWARE. These data enable analysis of the system
operation and provide detailed information for
troubleshooting, Operation monitoring with BEST
SOFTWARE.
KT-230-2
, window P
S
RESSURE
, enter Y
.
ES
IGH
P
S
OW
RESSURE
WITCH
. Basic setting: 33 bar /
all M
S
adjust.
AIN
ETUP
,
WITCHES
in the
P
-
RES
: V
,
ALUE
29