Terminals Recommended For Power Cables; Output Connections - WEG CFW-11W G2 RB Series User Manual

Regenerative frequency converter
Hide thumbs Also See for CFW-11W G2 RB Series:
Table of Contents

Advertisement

Use the cables with the gauge indicated in
Model
UP11-02 G2
UP11-01 G2
UP11W-01 G2

3.4.7 Terminals Recommended for Power Cables

Cable Gauge
Screw
Manufacturer Lug Terminal, Code
[mm²]
Hollingsworth
95
M12
Hollingsworth
120
M12
Burndy (FCI)
Hollingsworth
150
M12
Burndy (FCI)
Hollingsworth
185
M12
Burndy (FCI)
Hollingsworth
300
M12
Burndy (FCI)

3.4.8 Output Connections

The DC link and each UP11 G2 or UP11W G2 can be interconnected with flexible braids as in the example of
Figure 3.38 on page
3-34, sized to withstand the DC link current, according to
3.39 on page 3-34
shows an example of a flexible braid used by WEG.
Table 3.19 on page 3-33
Table 3.19: Grounding cables
Current (A)
Voltage (V)
634
380-480
515
496
500-600
380
439
660-690
340
780
500-690
640
Table 3.20: Terminals recommended for power cables
RM95-12
Tyco
XCT 95-12
RM120-12
YA28L
RM150-12
YA30L
RM185-12
YA31L
RM300-12
YA36L2
Installation and Connection
to ground the UP11 power units.
Minimum Cable Cross
Duty
Section (mm²)
ND
HD
ND
HD
ND
HD
ND
(2X) 120
HD
(2X) 95
Crimping Tool, Code
Hydraulic tool H6-500
UNIPRESS 6/120 +COF+CHARG
Item TE: 2107475-2
Hydraulic tool H6-500
Tool without die: MY29-3 or Y644 or Y81
Tool+die: Y35 or Y750 / U29RT
Hydraulic tool H6-500
Tool without die: Y644 or Y81
Tool+die: Y35 or Y750 / U30RT
Hydraulic tool H6-500
Tool without die: Y644 or Y81
Tool+die: Y35 or Y750 / U31RT
Hydraulic tool H6-500
Tool without die: Y644 or Y81
Tool+die: Y35 or Y750 / U36RT
Table 8.1 on page
300
185
185
120
150
120
Number of
Crimps
1
1
1
1
1
1
1
1
1
1
8-2.
Figure
CFW-11MW G2 RB | 3-33
3

Advertisement

Table of Contents
loading