WEG CFW-11W G2 RB Series User Manual page 100

Regenerative frequency converter
Hide thumbs Also See for CFW-11W G2 RB Series:
Table of Contents

Advertisement

Model
Power Supply [Vrms]
Nº of UP11
Rated Input Current [Arms]
Overload
Current
[Arms]
(3)
Normal
Switching Frequency [kHz]
Duty (ND
Rated output current [Acc]
Dissipated Power
[kW]
(4)
Rated Input Current [Arms]
Overload
Current
[Arms]
(3)
Heavy
Switching Frequency [kHz]
Duty (HD)
Rated Output Current [Acc]
Dissipated
Power
[kW]
(4)
Note:
(1) For the CFW11M G2 RB converter, steady-state rated current in the following conditions:
- Indicated switching frequency. It is not possible to use the CFW-11M G2 RB converter with switching frequency of 2.0 kHz, 5 kHz and 10 kHz.
- Ambient temperature around the converter as specified in
55 º C, the output current must be derated by 2 % for each ºC above the maximum temperature specified.
- Air relative humidity: 5 % to 95 % non-condensing.
- Altitude: 1000 m. Above 1000 m up to 4000 m, the output current must be derated by 1 % for each 100 m above 1000 m.
- Environment with pollution degree 2 (as per EN50178 and UL508C).
(2) For the CFW11W G2 RB converter, steady-state rated current in the following conditions:
- Indicated switching frequency. It is not possible to use the CFW-11W G2 RB converter with switching frequency of 2.0 kHz, 5 kHz and 10 kHz.
- Ambient temperature around the converter as specified in
55 º C, the output current must be derated by 0.5 % for each º C above the maximum temperature specified.
- Coolant input temperature as specified in
output current must be derated by 1 % for each º C above the maximum temperature specified.
- Coolant flow as specified in
Chapter 3 INSTALLATION AND CONNECTION on page
- Air relative humidity: 5 % to 95 % non-condensing.
- Altitude: 1000 m. Above 1000 m up to 4000 m, the output current must be derated by 1 % for each 100 m above 1000 m.
- Environment with pollution degree 2 (as per EN50178 and UL508C).
(3) One overload every 10 minutes.
Table 8.1 on page 8-2
and 3 s). The complete overload curves of the IGBTs for Normal Duty (ND) and Heavy Duty (HD) are presented in
the converter operating conditions, such as air temperature around the converter or coolant temperature, the maximum time for operation of the converter
under overload may reduce.
Table 8.2: Technical data of the CFW11W G2 RB converter
CFW11W G2
0780 T 6 O RB
1
780
1 min
858
3 s
1170
2.5
897
For the Coolant
11.7
For the Air
0.2
640
1 min
960
3 s
1280
2.5
736
For the coolant
9.2
For the air
0.2
Chapter 3 INSTALLATION AND CONNECTION on page
Chapter 3 INSTALLATION AND CONNECTION on page
Chapter 3 INSTALLATION AND CONNECTION on page
and
Table 8.2 on page 8-3
CFW11W G2
CFW11W G2
1482 T 6 O RB
2223 T 6 O RB
500...690
2
3
1482
2223
1630
2445
2223
3335
2.5
2.5
1704
2556
23.4
35.1
0.4
0.6
1216
1824
1824
2736
2432
3648
2.5
2.5
1398
2098
18.4
27.6
0.4
0.6
3-1. For higher temperatures, limited to 55 º C, the
3-1.
contain only two points of the overload curve (actuation time of 1 min
Technical Data
CFW11W G2
CFW11W G2
2964 T 6 O RB
3705 T 6 O RB
4
5
2964
3705
3260
4076
4446
5558
2.5
2.5
3409
4261
46.8
58.5
0.8
1.0
2432
3040
3648
4560
4864
6080
2.5
2.5
2797
3496
36.8
46.0
0.8
1.0
3-1. For higher temperatures, limited to
3-1. For higher temperatures, limited to
Figure 8.1 on page
8-4. Depending on
CFW-11MW G2 RB | 8-3
8