Installation and Connection
3
Figure 3.53: ICUP shield fastened to the panel
The control rack must be grounded using a flat flexible braid with minimum width of 5 mm and minimum section
of 3 mm² with standard FASTON terminal 6.35 mm (E.g.: TYCO 735075-0 and 180363-2) and lug terminal M4;
see
Figure 3.54 on page
3-45.
Flexible braid
Figure 3.54: Control rack grounding
The panel door must be grounded with a flexible braid.
Figure 3.55: Grounding of the panel door
CFW-11MW G2 RB | 3-45