WEG CFW-11W G2 RB Series User Manual page 67

Regenerative frequency converter
Hide thumbs Also See for CFW-11W G2 RB Series:
Table of Contents

Advertisement

Installation and Connection
3
Figure 3.58: Connector XC1 and switches to select the signal type of the analog inputs and outputs
As factory default, the analog inputs and outputs are selected within the range from 0 to 10 V; they can be changed
using switch S1.
Table 3.32: Configurations of the switches to select the signal type of the analog inputs and outputs
Signal
AO1
AO2
The parameters related to AO1 and AO2 must also be set according to the selection of the switches and desired
values.
For the correct connection of the control, use:
1. Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2. Maximum torque: 0.5 N.m (4.50 lbf.in).
3. Wiring on XC1 must be done with shielded cables separated from the other wiring (power, control in 110/220V,
etc.), according to
perpendicularly, keeping the minimum separation distance of 5 cm at the crossing point.
3-48 | CFW-11MW G2 RB
ON
1 2 3 4
1
XC1
29
Factory Default Function
DC Link voltage
Input current
Table 3.33 on page
3-48. If those cables must cross other cables, it must be done
Table 3.33: Wiring separation distance
Wiring Length
≤ 30 m
> 30 m
Slot 5
Slot 1 (white)
Setting
Selection
Element
OFF: 4 to 20 mA / 0 to 20 mA
S1.1
ON: 0 to 10 V (factory default)
OFF: 4 to 20 mA / 0 to 20 mA
S1.2
ON: 0 to 10 V (factory default)
Minimum Separation Distance
≥ 10 cm
≥ 25 cm
Factory
Setting
ON
ON