Fault/Alarm
F091
External Fault
F099
Invalid Current Offset
F101
Invalid Voltage Offset
A105
Injection of Reactive Power in
the Line
F151
Flash Memory Module Fault
A152
High Internal Air Temperature
F153
Internal Air Overtemp.
A156
Undertemperature
F156
Undertemperature
A177
Fan Replacement
A181
Clock with Invalid Value
F182
Pulse Feedback Fault
F183
Overload
IGBTs+Temperature
A300
High Temperature
IGBT U B1
F301
Overtemperature
IGBT U B1
A303
High Temperature
IGBT V B1
F304
Overtemperature
IGBT V B1
A306
High Temperature
IGBT W B1
F307
Overtemperature
IGBT W B1
A309
High Temperature
IGBT U B2
Description
External alarm via DI.
Note:
- It is necessary to program DI for "without external
fault".
Current measurement circuit has a value out of the
standards for zero current.
Offset calculation error in the reading of the input
voltage (synchronism).
Alarm of injection of reactive current in the line.
Fault on the Flash Memory Module (MMF-01).
High internal air temperature alarm.
Measured temperature above 75 ºC (167 °F).
Note:
- It can be disabled by setting P0353 = 1 or 3.
Internal air overtemperature fault.
Measured temperature above 80 ºC.
Only one sensor indicates temperature below
-30° C (-22 °F).
Undertemperature fault measured on the IGBT
temperature sensors.
Alarm to replace the fan (P0045 > 50000 hours).
Note:
- It may be disabled by setting P0354 = 0.
Alarm of clock with wrong time.
Pulse feedback fault.
Overtemperature
related
to
protection.
Alarm of high temperature measured on the
temperature sensor (NTC) of the IGBT of phase U of
book 1. Measured temperature above 110 ºC (230 ºF).
Fault
of
overtemperature
measured
temperature sensor (NTC) of the IGBT of phase U of
book 1. Measured temperature above 115 ºC (239 ºF).
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase V of
book 1. Measured temperature above 110 ºC (230 ºF).
Fault
of
overtemperature
measured
temperature sensor (NTC) of IGBT of phase V of
book 1. Measured temperature above 115 ºC (239 ºF).
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase W of
book 1. Measured temperature above 110 ºC (230 ºF).
Fault
of
overtemperature
measured
temperature sensor (NTC) of IGBT of phase W of
book 1. Measured temperature above 115 ºC (239 ºF).
Alarm of high temperature measured on the
temperature sensor (NTC) of IGBT of phase U of
book 2. Measured temperature above 110 ºC (230 ºF).
Troubleshooting and Maintenance
Wiring at the DI1 to DI8 inputs open (programmed
for "without external fault").
Defect on internal circuits of the converter.
Main contactor closed before the pre-charge is
completed.
CPU was reset and the main contactor did not
open.
Line voltage too above the rated value.
P0180 too low.
Flash memory module defective.
Flash memory module not well fitted.
High ambient temperature around the converter
(> 30 °C (86 °F)).
High temperature inside the panel (> 45 °C (113 °F)).
Ambient temperature around the converter ≤
-30 °C (-22 °F).
Ambient temperature around the converter ≤
-30 °C (-22 °F).
Maximum number of the heatsink fan operating
hours exceeded.
Necessary to set the date and time in P0194 to
P0199
HMI battery low, defective or not installed.
Defect on the internal circuits of the converter.
Defect on the fiber optic.
Defect on cables XC10A, B, C, D or E.
IGBT
overload
High ambient temperature around the converter.
Operation with overload.
High ambient temperature (> 45 °C (113 °F)) and
high output current.
Locked or defective fan.
Book heatsink fins too dirty, hindering the air flow.
on
the
High coolant temperature (> 45 °C (113 °F) see
Item 3.2.6 Cooling System on page
high output current.
Coolant flow < 20 l/min or clogged tubing.
UP11W heatsink or system heat exchanger rust
inside due to coolant out of the specifications (see
on
the
Item 3.2.6 Cooling System on page
Fault in the pumps.
on
the
Possible Causes
3-17) and
3-17).
CFW-11MW G2 RB | 6-3
6