Energization and Start-Up
17. The display must show the standard monitoring screen
turn on and remain on in green.
18. Follow the start-up routine of the output inverters according to the directions contained in the specific manual.

5.2 START-UP

The start-up can be simply explained in three steps, using the programming resources with the existing parameter
groups Oriented Start-Up and Basic Application.
Sequence:
1. Set the password to change parameters.
2. Execution of the Oriented Start-Up routine.
3. Setting the parameters of the Basic Application group.
5

5.2.1 Password Setting in P0000

Step
Action/Result
Monitoring Mode
Press "Menu" (right
1
soft key)
Group "00 ALL
PARAMETERS" is
2
already selected
Press "Select"
Parameter "Access to
Parameters P0000: 0"
3
is already selected
Pressione "Select"
To set the password,
press the Up Arrow
until number
4
5 is displayed in the
keypad

5.2.2 Oriented Start-up

To simplify the setting of the converter, there is a parameter group called Oriented Start-Up. Within this group is
parameter P0317, which can be used to access the Oriented Start-Up.
The Oriented Start-up routine shows the main parameters on the HMI in a logical sequence, so that their setting,
according to the operating conditions, prepares the inverter for operation according to the line used.
In order to enter the Oriented Start-Up routine, follow the sequence shown in
changing P0317 = 1, and then setting the other parameters as they are displayed on the HMI.
The setting of the parameters displayed in this operating mode automatically changes the content of other internal
variables and/or parameters of the converter.
During the Oriented Start-Up routine, the "Config" (Configuration) status will be indicated on the top left part of
the HMI.
5-2 | CFW-11MW G2 RB
Display Indication
Run
RB + LOC
618 V
400
A
618
V
380
V
15:45
Menu
Run
RB + LOC
618V
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
15:45
Select
Run
RB + LOC
618V
Access to Parameters
P0000:
0
Line Voltage
P0002:
380 V
Return
15:45
Select
Run
RB + LOC
618V
P0000
Access to Parameters
0
Return
15:45
Save
Figure 5.1: Sequence for allowing parameter change via P0000
(Figure 4.3 on page 4-3
Step
Action/Result
When number 5 is
displayed in the keypad,
5
press "Save"
If the setting has been
properly performed,
the keypad should
6
display "Access to
Parameters P0000: 5"
Press "Return" (left
soft key)
7
Press "Return"
The display returns to
8
the Monitoring Mode
Figure 5.2 on page
(a)), the status LED must
Display Indication
Run
RB + LOC
618V
P0000
Access to Parameters
5
Return
15:45
Salvar
Run
RB + LOC
618V
Access to Parameters
P0000:
5
Line Voltage
P0002:
380V
Return
15:45
Select
Run
RB + LOC
618V
00 ALL PARAMETERS
01 PARAMETER GROUPS
02 ORIENTED START-UP
03 CHANGED PARAMETERS
Return
15:45
Select
Run
RB + LOC
618V
400
A
618
V
380
V
15:45
Menu
5-3, first