The Reader.txt (Reader table) has the following content:
; Reader list for the example access control system
; ID ZM TM RefLocation RefAction PinGeneral
1 1 320 0 0 0
2 1 000 1 1 0
3 1 010 2 0 0
4 1 011 2 2 0
The data record with the ID 1 stands for the ZK-MasterIV and receives number 1 as access master (ZM
- Zutrittsmaster). The access master always receives the number 320 as TM value, that means it always
receives the bus number 32. Because the ZK-MasterIV is not necessary for controlling a relay or door
opener, you can enter 0 in the Location table for the reference to a data record. The same applies to the
reference to the Action or as PinGeneral.
The data record with the ID 2 stands for the TS TMR33-LTM and is managed via the access master
(ZM) 1. The module receives the number 000 as TM value; both numbers on the left stand for the bus
no. 0 and the number on the right 0 marks the communication via RS485. At this place only 0 or 1 are
permitted. This module is assigned to the room with the location-ID (RefLocation) 1. If an access is
authorized, the action (RefAction) 1 shall be carried out. A PIN for an access without card (PinGeneral)
is not used; therefore, the value at this place is 0.
The data record with the ID 3 stands for the TS TMR33-TM and is managed via the ZM 1. The module
receives the number 010 as TM value. This value corresponds to the bus no. 1 with a communication
via RS485. The module is assigned to the room with the location-ID (RefLocation) 1. Because the door
module has no reader, it cannot set off an action in this example. As a note: it would be possible to set
off an action via the digital or analogous inputs of the door module. It is also not possible to enter a PIN,
thus, PinGeneral = 0.
The data record with the ID 4 stands for the TS TMR33-L and is also managed via the ZM 1. The
module receives the number 011 as TM value. This value corresponds to the connection to the module
with the bus no. 1 via RS232 via a stub line (data record 3). This module is assigned to the room
with the location-ID (RefLocation) 2. If an access is authorized, the action (RefAction) 2 shall be car-
ried out. A PIN for an access without card (PinGeneral) is not used; therefore, the value at this place is 0.
The Identification.txt (Identification table) has the following content:
; Identification list for the example access control system
; ID Group Pin Menace ActiveStart ActiveEnd ActiveGeneral
1111 1 1111 511 2005-01-01 2008-01-01 1
2222 2 2222 522 2005-01-01 2008-01-01 1
You can adjust the ID or the PIN and the menace code to your requirements, dependent on the card
number you use. The time domain for ActiveStart and ActiveEnd can be set as well. If you do not have
modules with a keyboard, you can also set the PIN and menace code on 0.