Configuration
September 2019
From the HOME screen, enter the Fast Key sequence
Fast Keys
Procedure
1. From the Home screen, select 2: Configure
2. Select 2: Manual Setup
3. Select 1: Measurements
4. Select 1: Dial/Pressure
5. Select 3: Over-Press Ind
6. Follow the commands to perform the procedure.
3.9.2
Acknowledge and reset overpressure notification
From the HOME screen, enter the Fast Key sequence
Fast Keys
Procedure
1. From the Home screen, select 3: Service Tools.
2. Select 3: Maintenance.
3. Select 3: Acknowledge Over-Pressure.
4. Follow the commands to perform the procedure.
30
Note
When the parameter has been set to activate, the notification must be
acknowledged and cleared for the device to return to normal operation.
2, 2, 1, 1, 3
3, 3, 3