If this parameter is set to Reset the device and continue
communicating [1] and a bus-off event is detected the
VLT 2800/FCD 300 will try to reset and re-initialise
the CAN chip and to continue communication.
833 Fieldbus enable
(FIELDBUS ENABLE)
Value:
✭Disabled (DISABLE)
Enabled (ENABLE)
Function:
This parameter allows to disable the
communication interface.
Description of choice:
Select Enable [1] to start the DeviceNet communication.
If Disable [0] is selected no communication warning will
appear, since the communication interface is disabled.
NB!:
Note that a change of this parameter is
first executed at next power up.
834 Filter Mask for status word
(COS FILTER 1)
Value:
0000 - FFFF Hex
Function:
When operating in COS (Change-Of-State) it is
possible to filter out bits in the status word that
should not be send if they changes.
Description of choice:
Setup the filter mask for the status word.
NB!:
For further information, see the section
Change of state, Cos.
835 Filter Mask for main actual value
(COS FILTER 2)
Value:
0000 - FFFF Hex
Function:
When operating in COS (Change-Of-State) it is
possible to filter out bits in the Main actual value
that should not be send if they changes.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
40
VLT
Description of choice:
Setup the filter mask for the Main actual value.
836 Filter Mask PCD 1
(COS FILTER 3)
Value:
0000 - FFFF Hex
Function:
[0]
When operating in COS (Change-Of-State) it is
[1]
possible to filter out bits in PCD 1 that should
not be send if they changes.
Description of choice:
Setup the filter mask for PCD 1.
837 Filter Mask PCD 2
(COS FILTER 4)
Value:
0000 - FFFF Hex
Function:
When operating in COS (Change-Of-State) it is
possible to filter out bits in PCD 2 that should
not be send if they changes.
Description of choice:
Setup the filter mask for PCD 2.
✭ FFFF Hex
838 EDS Data Types
(EDS DATA TYPES)
Value:
Errata 1 (ERRATA 1)
✭Errata 2 (ERRATA 2)
Function:
In this parameter it is possible to select between
two data types when uploading an EDS file from the
VLT frequency converter. The current versions of the
configuration tools like DeviceNet Manager and RS
Networx can only handle data type Errata 1.
Description of choice:
Select Errata 1 if DeviceNet Manager or RS
✭ FFFF Hex
Networx version 3.00 is used.
Select Errata 2 if DeviceNet Manager or RS Networx
version 3.11 or higher is used.
MG.90.B2.02 - VLT is a registered Danfoss trade mark
®
2800 / FCD 300 DeviceNet
✭ FFFF Hex
✭ FFFF Hex
[0]
[1]