FC100 Series User Manaul

Group P5: PLC Control ( Special Operation)

P500

PLC memory mode

Setting Range:0~1
Explanation:
0: Do not remember
In the operational process of PLC program, P500 will choose not to remember.
When machinery stops because of fault or other reasons, inverter will not
remember status before the stopping. After restart, running begins from initial
state.
1: Remember
In the running of PLC program, P500 will select to remember. When it stops
because of fault or other reasons, inverter will remember status before
stopping. After restart, inverter will continue operating according to program.
Attention: power cannot be cut off.
Stop,power cut and power on, inverter will not remember status before power
cut off. After restarting, inverter will run according to initial state of program.
P501

PLC start mode

Setting Range:0~1
Explanation:
0: Invalid (PLC can not start)
P501 determines PLC start mode of inverter.
P501=0, means PLC is invalid. The inverter is operated by common mode.
When P501=1, PLC will start. The inverter select PLC program to run.
Under the status of PLC start, when various running orders and programs,
inverter will choose the highest level to run according to priority level.
Pre cedence level
High — low
0: Do not remember
Priority level
Item
1
Jog
External multi -speed
2
Internal multi -speed
3
4
PID
Triangular wave
5
6
Winding
7
Inverter setting mode
Chapter 6 Description of parameter setting
Unit:1
1: Remember
Unit:1
1: Valid (PLC start)
79
Default value 0
Default value 0
6