Chapter 6 Description of parameter setting
Parameter P409 is the torque limit level during acceleration. When output
current reaches the setting value, inverter will stop accelerating, and when
current is below the set value, inverter resume the accelerating.
100% current is the rated current of inverter, when P409 is set to be 0, then
accelerating torque limit is invalid, and it does not have protecting function.
P410
Constant-speed torque limiting level
Setting Range:0~200
6
Parameter P409 is the torque limit level during constant speed. When output
current reaches the setting value, inverter automatically reduce the output
frequency in order to reduce the load. When the output current drops, inverter
increase output frequency to the setting (100% current is rated current of
inverter).
When P410 is set to be 0, constant-speed torque limiting level is invalid and
cannot protect.
P410
Deceleration over-voltage prevention selection
Setting Range:0~1
72
FC100 Series User Manaul
Default value 00
Unit:1
Default value 1
Unit:1