Tracing Start; Stop Mode Selection - Janson Controls FC100 Series Manual

Table of Contents

Advertisement

FC100 Series User Manaul
Chapter 6 Description of parameter setting

1: Tracing start

Tracing start is application for start after fault reset or instantaneous power
failure. Using tracing start function, inverter can automatically detect the rotation
speed and rotation direction of motor, the output the starting frequency and
voltage accordingly.
Attention: when inverter starts in tracing start mode, inverter will have speed
tracing in the sequence of high to low frequency.
High current is likely in start, it is also possible to cause current. Therefore, you
need to have over current level setup (P409 setup).
6
The specific value depends on the load
In addition, when the value of P409 is too low,it may lead to a long start time. If
over current in the speed tracing, inverter will pause the speed tracing.
P201

Stop mode selection

Factory Setting: 0
SettingRange:0-1Unit:1
Explanation: 0: Deceleration to stop
1: Coasting stop
You can choose a suitable stop mode according to the actual load.
0: Deceleration to stop
Once inverter receives stop command, it will reduce the output frequency
according to the deceleration time.
52