Chapter 6 Description of parameter setting
P107

ACC time

P108

DEC time

SettingRange:0.1s~999.9s
Acc time refers to the time for inverter to reach the max. frequency from 0.00Hz.
Dec time refers to the time for inverter to lower to 0.00Hz from max. frequency.
The Default Acc/Dec time is the primary Acc time/ Dec. time. Other Acc time or
Dec time can be selected via external terminal.
6
P109

V/F maximum voltage

SettingRange:V/F intermediate voltage-500.00Unit:0.1
P110

V/F fundamental frequency

SettingRange:V/F intermediate frequency ~ max. frequencyUnit:0.1
P111
V/F intermediate voltage
SettingRange:V/F minimum voltage ~ V/F maximum Unit:0.1
P112
V/F intermediate frequency
SettingRange:V/F minimum frequency ~ V/F fundamental Unit:0.1
P113
V/F minimum voltage
SettingRange:0.0 ~ V/F intermediate voltage Unit:0.1
P114
V/F minimum frequency
SettingRange:0.0 ~ V/F intermediate frequencyUnit:0.1
F
48
FC100 Series User Manaul
Factory Setting: change
Factory Setting: change
Factory Setting: 380
Factory Setting: 50
Factory Setting: change
Factory Setting: 2.5
Factory Setting: 15
Factory Setting: 1.25