Initial installation
1 Untighten the screw but do not remove it and pull up the reflector.
2 Place the battery's connector to the corresponding connector on the P.C.B.
3 Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F
type 2x1mm² or any other type, at least equal to it's mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is important
to ensure the ΙΡ rating). Install the included gaskets in to the cable entry holes (verify that are
not deformed). Make a hole in the center by using a small screwdriver. Pass the round cable
through the gasket. Detach the power terminal, connect the wires as shown in the picture and
attach the power terminal (10A max). If you use a module pass the 2 signal cables on the A, B
terminals Minding the correct polarity. Depending on the module that will be used, the cables that
will be used, have different names. In A, signal +L, C are also connected, while signals -L,
NC/NO in the terminal B.
4 Refit the reflector (mind the correct orientation), tighten the screw securely and the luminaire
is ready for mounting.
NOTE!! After finishing the installation you must power the luminaire for at least 24 hours in
order to completely charge the battery. The rated autonomy duration can be achieved after
that time.
Battery replacement.
It can be done only by a competent person and after the mains interruption.
1. Remove the luminaire from the suspended ceiling (figure 3).
2. Follow the step 1 of the installation instructions.
3. Disconnect the connector and remove the old battery.
4. Connect the new battery with the same type (step 2 of the installation instructions) and place it in
the position of the old one.
5. Replace the removed parts (step 1 and 4) and power the device.
Important notice for the installed luminaires in one area !!!
The installer must connect the battery's connector first and then should power the luminaire.
The time between batteries connection must be, at least 1.5 minute.
With this variation, it is ensured that the non synchronized Automatic Autonomous Test for two or more
luminaires installed in one area, is not conducted in the same day.