Self testing maintained emergency luminaries

Advertisement

Quick Links

SELF TESTING MAINTAINED EMERGENCY LUMINARIES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (230V AC / emergency)
VIEWING DISTANCE
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
Each luminaire must be permanently
connected to mains power supply. In normal
operation the illumination LEDs are lit as well
as the green indicating charge LEDs when
the battery is charging. In case of a mains
power supply failure the luminaire will light
the led strip automatically in emergency
mode. When the mains power supply is
r e s t o r e d t h e d e v i c e t u r n s t o n o r m a l
operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
Battery Charging
The
battery
charging
controlled. Thereby, the best possible battery
maintenance is achieved, as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Battery Cut-off
The luminaire enters in this operation when
Page 1 from 4
3.6V/600mAh(Ni-Cd)
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
is
completely
(for LED MODULE Specs. see page 3)
GR-2100/ST
220-240V AC/50-60Hz
3.4W / 3.6VA
Battery charge Fault indication LEDs, TEST button
16 h
1.5 h
12 White LEDs
110lm / 110lm
22m
IP30
5 to 40 C
up to 95%
ABS/PC,PC
292 x 111 x 54 mm
453gr.
3 years (1 year for the battery)
the mains power supply fails and battery has
lost all its energy. During this operation the
luminaire enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Manual Operational Test
This test can be done by pressing the test
button. The light source and the emergency
circuit of the device is monitored for 3 sec.
The manual test can be conducted only if the
mains power supply and the battery is
connected.
During
indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device's back up operation
and
emergency
conducted automatically every 6 months. In
order to be performed, the mains power
GR-2110/ST
3.6V/1.5Ah (Ni-Cd)
24 h
3 h
o
532gr.
this
test
period
duration.
This
test
923211004_09_004
all
is

Advertisement

loading

Summary of Contents for olympia electronics GR-2100/ST

  • Page 1 TYPICAL WEIGHT 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products Olympia Electronics - European manufacturer GENERAL the mains power supply fails and battery has These luminaires are used indoors (ta 40 C) lost all its energy.
  • Page 2 supply and the battery should be connected pulling out the battery’s connector. and fully charged. If the battery is not fully charged, the test is postponed until the 4. I s not allowed to discard batteries in to battery is completely charged. If during this common trash bins, they must be test, the autonomy is less than nominal then discarded only...
  • Page 3 After finishing the installation you must power the luminaire at least for 24 hours for battery charging to perform the nominal autonomy. LED MODULE CHARACTERISTICS GR-2100/ST GR-2110/ST Manufacturer Olympia Electronics S.A Model Number 3105165 Voltage Range 8.7-10.8VDC Nominal Power 780mW...
  • Page 4 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-2110/st