WATERPROOF SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Mh)
BATTERY PROTECTION
INDICATIONS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSIONS
WEIGHT
GUARANTEE
GENERAL
These devices are used indoors (ta 40 C) in
places where emergency luminaires are
needed. The luminaires GR-490/WP and
GR-492/WP are suitable for corridors lighting
and the GR-491/WP and GR-493/WP for
open area lighting. Each device must be
permanently connected to mains power
supply. In normal operation the battery is
charging. In case of a mains power supply
failure, the device enters emergency mode
and the illumination LED turns on. When the
mains power supply is restored the device
turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 3.
Battery Charging
The battery charging is completely controlled
by microprocessor and is protected from
complete discharge and overcharge.
Battery Cut-off
The luminaire enters in this mode when the
mains power supply fails and battery has lost
its energy. During this mode the luminaire
enters the idle state and battery consumption
Page 1 from 7
GR-490/WP
LED Charge , Lamp Fault LED, Battery Fault LED / Magnetic Test Contanct
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
158 x 158 x 60,4mm (without decorative bezel) - 195 x 195 x 60,4 (with decorative bezel)
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
(for LED MODULE specifications see page 7)
GR-491/WP
220-240V AC / 50-60Hz
3.9W / 4.4VA
4.8V/1.2 Ah
Deep discharge and overcharge protection
24 hours
1.5 hour
1 white power LED
280lm
IP65
5 to 40 C
Up to 95%
ABS/PC, PC
576gr.
3 years (1 year for the battery)
is negligible, in order to be protected from
deep discharge.
Manual Test
This test can be done by using the A-1900
card as described on page 6. The light source
and the emergency circuit of the device are
tested. The manual test can be conducted
only if the mains power supply and the battery
are connected. During this test period the
LAMP TEST LED will blink.
Manual Autonomy Test
A duration test can be conducted by holding the
A-1900 card steadily for 5 to 10 seconds. In
order to be performed, the mains power supply
and the battery should be connected. The
luminaire enters emergency mode, the charge
LED is turned OFF and the Battery Fault led
starts to blink. The test is performed until the
battery is fully discharged.If at the end of the
test the autonomy is low then the Battery Fault
LED will be ON. If the result of the test is good
then the luminaire enters charging mode and
the Charge led starts to blink until the batteries
are fully charged.
GR-492/WP
GR-493/WP
3 hour
140lm
o
923493000_09_003