Download Print this page

Installation Instructions - olympia electronics GR-290/WP Manual

Waterproof self testing non maintained spot light emergency luminaries with 1 white power led

Advertisement

stated
in
the
characteristics. During emergency mode, a
light source test is also performed.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance
or testing must be done by authorized
personnel only.
2. The device must be connected to the
m a i n s p o w e r s u p p l y t h r o u g h a f u s e
dependent by the total amount of the line's
power load.
3. The replacement of the battery and the
light source must be done using parts of the
same type, by the manufacturer or by a
competent person.
4. In case of inactive use for a period greater
than 2 months, disconnect the battery by
pulling out the battery's connector.
5. I
t i
s not allowed to discard batteries
into common trash bins, they must
b e d i s c a r d e d o n l y
recycling points. Do not incinerate.
Initial installation
1 Untighten the screw and pull up the reflector.
2 Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type 2x1mm²
or any other type, at least equal to it's mechanical and electrical properties). ATTENTION!!
The cable must not be deformed in any way (This requirement is important to ensure the ΙΡ
rating). Install the included gaskets in to the cable entry holes (verify that are not deformed). Make a
hole in the center by using a small screwdriver. Pass the round cable through the gasket. Detach the
power terminal, connect the wires as shown in the picture and attach the power terminal (10A max).
3 Place the battery's connector to the corresponding connector on the P.C.B.
4 Refit the reflector (mind the correct orientation), tighten the screw securely and the luminaire is ready
for mounting.
NOTE!! After finishing the installation you must power the luminaire for, at least, 24 hours for
battery charging to perform the nominal autonomy.
Page 2 from 5
list
of
the
technical
i n b a t t e r y

INSTALLATION INSTRUCTIONS

Cable
entry
hole
1
The light source contained in this
luminaire shall only be replaced by the
manufacturer, or his agent, or a similar
qualified person.
NOTE! The light source is non-user
replaceable.
2
L
N
3
923293005_09_004

Advertisement

loading

This manual is also suitable for:

Gr-291/wpGr-292/wpGr-293/wp