Addressable self testing non-maintained emergency ceiling mounted luminaires

Advertisement

Quick Links

ADDRESSABLE SELF TESTING NON-MAINTAINED EMERGENCY CEILING MOUNTED LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Mh)
BATTERY PROTECTION
INDICATIONS
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSIONS
WEIGHT
GUARANTEE
GENERAL
These devices are used indoors (ta 40 C) in
places where emergency luminaires are
needed. The luminaires GR-490/ADR and
GR-492/ADR are suitable for corridors
lighting and the GR-491/ADR and GR-
493/ADR for open area lighting. Each device
must be permanently connected to mains
power supply. In normal operation the
battery is charging. In case
power supply failure, the device enters
emergency mode and the illumination LED
turns on. When the mains power supply is
r e s t o r e d t h e d e v i c e t u r n s t o n o r m a l
operation.
INSTALLATION
To install the luminaire follow the installation
instructions οn page 3.
Battery Charging
The battery charging is completely controlled
by microprocessor and is protected from
complete discharge and overcharge.
Battery Cut-off
The luminaire enters in this mode when the
mains power supply fails and battery has lost
its energy. During this mode the luminaire
Page 1 from 9
GR-490/ADR
LED Charge , Lamp Fault LED, Battery Fault LED / Magnetic Test Contanct
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
158 x 158 x 60,4mm (without decorative bezel) - 195 x 195 x 60,4 (with decorative bezel)
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
of a mains
(for LED MODULE specifications see page 6)
GR-491/ADR
220-240V AC / 50-60Hz
3.9W / 4.4VA
4.8V/1.2 Ah
Deep discharge and overcharge protection
24 hours
1.5 hour
1 white power LED
280lm
IP40
5 to 40 C
Up to 95%
ABS/PC, PC
600gr.
3 years (1 year for the battery)
enters the idle state and battery consumption
is negligible, in order to be protected from
deep discharge.
Manual Test
This test can be done by using the A-1900
card as described on page 6. The light source
and the emergency circuit of the device are
tested. The manual test can be conducted
only if the mains power supply and the battery
are connected. During this test period the
LAMP TEST LED will blink.
Manual Autonomy Test
A duration test can be conducted by holding the
A-1900 card steadily for 5 to 10 seconds. In
order to be performed, the mains power supply
and the battery should be connected. The
luminaire enters emergency mode, the charge
LED is turned OFF and the Battery Fault led
starts to blink. The test is performed until the
battery is fully discharged.If at the end of the
test the autonomy is low then the Battery Fault
LED will be ON. If the result of the test is good
then the luminaire enters charging mode and
the Charge led starts to blink until the batteries
are fully charged.
GR-492/ADR
GR-493/ADR
3 hour
140lm
o
923493003_09_001

Advertisement

loading

Summary of Contents for olympia electronics GR-490/ADR

  • Page 1 These devices are used indoors (ta 40 C) in is negligible, in order to be protected from places where emergency luminaires are deep discharge. needed. The luminaires GR-490/ADR and GR-492/ADR are suitable for corridors Manual Test lighting and the GR-491/ADR and GR- This test can be done by using the A-1900 493/ADR for open area lighting.
  • Page 2 Automatic Operational Test ΑΤΤΕΝΤΙΟΝ!!! This test includes all the operations that are 1. Operations for installation, maintainance provided in manual test and is conducted or testing must be done by authorized automatically every 15 days. In order to be personnel only. performed, the mains power supply and the 2.
  • Page 3: Installation Instructions

    4 Reinstall the diffusor and re-tighten the 4 screws in a diagonally manner with a torque of NOTE!! After finishing the installation you must power the luminaire for at least 24 hours in order to completely charge the battery. The rated autonomy duration can be achieved after that time. GR-490/ADR, GR-492/WP/ADR GR-491/ADR, GR-493/ADR Open...
  • Page 4 MOUNTING IN SUSPENDED CEILING plastic mounting luminaire’s bracket base Required opening 14.5x14.5cm wall plug wall plug screws screws 1. Detach the front cover by applying pressure using a flat blade screw driver. Next, unfasten the four retaining screws (figure 1) without removing them and remove the diffusor. 2.
  • Page 5: Surface Mounting

    MOUNTING IN SUSPENDED CEILING SURFACE MOUNTING Other possible cable entry holes washer rabber o-ring 1. Detach the front cover by applying pressure using a flat blade screw driver. Next, unfasten the four retaining screws without removing them and remove the diffusor. 2.
  • Page 6 LED MODULE CHARACTERISTICS GR-490/ADR GR-491/ADR GR-492/ADR GR-493/ADR Olympia Electronics S.A. Manufacturer Model Number 0405183 Voltage Range 3-3,1V DC 2,8-2,9V DC Nominal Power fixed connection between main pcb and led module Connections Temperature (tc) 65 °C max. across the board Test and Faults Reset operations with the A-1900 card (not included and available after request).
  • Page 7 Dipswitch Dipswitch Dipswitch Dipswitch Address Address Address Address setting setting setting setting Page 7 from 9 923493003_09_001...
  • Page 8 Dipswitch Dipswitch Dipswitch Dipswitch Address Address Address Address setting setting setting setting Page 8 from 9 923493003_09_001...
  • Page 9: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.