Download Print this page

Installation Instructions; Maintained/Non-Maintained Operation; Jumper Selection; Battery Replacement - olympia electronics EASY LIGHT Series Manual

Non-maintained/maintained emergency luminaires

Advertisement

Reflector
Base plastic
4
Cable entry channels
Luminaire mounting holes
Base plastic
1 To install the luminaire you must dismantle it to 3 parts.
2 Place a flat blade screwdriver in the area Α to release the diffusor's plastic hook.
3 Place a flat blade screwdriver in the area B to release the reflector's plastic hook.
4 Use the included mounting parts to mount the base plastic. Pass the mains cable thru a cable
entry channel and secure it with a suitable bracket to ensure immobilization of the cable at a
distance of no more than 5cm from the luminaire's cable entry.
5 Place the battery's connector to the corresponding connector on the P.C.B.
6 Connect the mains cables to the respective detachable terminal block. Ν for neutral and L for
live wire.
7 Refit the removed parts in steps 2 and 3 (mind the correct orientation) and the luminaire is ready
to operate.

8. MAINTAINED/NON-MAINTAINED OPERATION

JUMPER SELECTION

You can choose the luminaire's operation.
When the jumper is installed (by default) on the middle and left
pins you select non-maintained operation. When the
jumper is installed on the middle and right pins you select
maintained operation.
NOTE!! After finishing the installation you must power the
device at least for 24 hours for battery charging to perform the
named autonomy.

Battery replacement.

It can be done only by a competent person and after the mains interruption.
1. Follow the step 2 and 3 of the installation procedure.
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step 5 of the installation procedure) and place it in
the position of the old one.
4. Follow the step 7 of the installation procedure and power the device.
Page 4 from 4

INSTALLATION INSTRUCTIONS

1
Diffusor
B
A
Cable
support
2
A
5
Non-maintained
operation
3
B
6
N
L
Maintained
operation
923312017_09_003

Advertisement

loading

This manual is also suitable for:

Easy light gr-310/15lEasy light gr-312/15l