Mounting/Dismounting Modules
Dismounting Sockets
Disconnecting Sockets
Release all bridge connectors before removing the controller
module and/or the terminal sockets and/or mixed I/O
modules from the DIN rail.
Press down at the same time both the gray side wings
next to the red button and then pull the bridge connector
out of the module.
Fig. 19
Releasing bridge connectors
Dismounting Controller / Terminal Sockets / Mixed I/O
Modules
Insert a screwdriver into the latch on the underside of the
module and lever the red latch 2–3 mm downwards. The
module can then be swung away from the rail.
Fig. 20 Releasing latch
EN1Z-0921GE51 R0315

Mounting/Dismounting Electronic Modules

Mounting Electronic Modules
NOTE:
Electronic modules can be removed from the
socket or inserted into the sockets without
switching off the power supply, but the resultant
behavior of connected field devices must be
taken into consideration.
Make sure that terminal socket und electronic I/O module
match; see Table 4 on page 5.
Make sure that the red locking mechanism is in the open,
i.e., left, position.
Gently push the electronic module onto the terminal
socket until snug.
Fig. 21
Inserting the electronic module
Lock the red locking mechanism by sliding it to the right.
Fig. 22
Locking the electronic module
NOTE:
The red locking mechanism will not close if the
electronic module is not properly mounted.