Connecting Field Devices - Honeywell Centraline LION Installation & Commissioning Instructions

Table of Contents

Advertisement

Wiring and Setting Up the System

Connecting Field Devices

Connecting Field Devices with Power Supply
Depending on the distance from the controller, field devices
can be supplied by the controller or need a separate
transformer, see Table 20 on page 12.
For fusing see section "Fusing Specifications" on page 9.
Example 1: Power Supply via Controller
 24 V actuator connected to an analog output module
 Less than 100 m away from the controller
F2
822
CLLIONLC01
F1
24 V~
1
230 V~
2
24 V0
11...18
9
Fig. 39
Power supply of field devices via I/O module
Example 2: Power Supply via Separate Transformer
 24 V actuator connected to an analog output module
 100 ... 400 m away from the controller
822
F1
CLLIONLC01
24 V~
1
230 V~
2
24 V0
11...18
Fig. 40
Power supply of field devices via a separate
transformer
EN1Z-0921GE51 R0315
24V
Y (0...10 Vdc)
1...8
Y
GND
max. 100 m
24 V0
230 V~
24 V~
F2
24V
Y (0...10 Vdc)
1...8
Y
GND
max. 400 m
Cabling Field Devices
Cable Routing
Route low-voltage signal and output cables separately from
mains cables.
Cable
Shielded
Unshielded
Table 26 Min. distances to power mains cables
All low-voltage signal and output cables should be regarded
as communication circuits in accordance with VDE 0100
and VDE 0800 (or NEC or other equivalent).
Cable Shielding
~
 If the general guidelines for cable routing are observed, it
is not necessary to shield field device signal and power
supply cables.
 If, for whatever reason, the routing guidelines cannot be
observed, the field device signal and power supply
cables must be shielded.
– Shielding of cables leading to field devices must be
grounded only at the cabinet end.
– The shield must not be terminated at the
CLLIONLC01.
~
28
Min. distance
10 mm (0.4 in.)
100 mm (4 in.)
LION System

Advertisement

Table of Contents
loading

Table of Contents