Connecting Via Lon Works; Connecting Via C-Bus; Connecting Hmis Or Laptops; Connecting Modems - Honeywell Centraline LION Installation & Commissioning Instructions

Table of Contents

Advertisement

LION System

Connecting via C-Bus

Via C-Bus, a LION Controller can be connected to other
controller systems to form a network.
Connecting to the Controller
Connect the C-Bus to the CLLIONLC01 as follows:
– Input to C-Bus terminals 8 and 9
– Output to C-Bus terminals 5 and 6
– Do not connect the C-Bus to the cabinet earth or any
other earth ground points
Setting C-Bus Termination Switch
Set the C-Bus termination switch S1 appropriately.
S1
9.6k
al l
76k
mi d
76k
end
C-Bus
Fig. 43
C-Bus termination switch S1
Switch
Baud rate
setting S1
9.6k all
Up to 9600 baud (default setting)
76k mid
Up to 76800 baud without bus termination
76k end
Up to 76800 baud with bus termination
Table 27 CLLIONLC01 C-Bus termination switch settings
How to Shield
In principle, data transmitting cables should be shielded in
case of RFI.
On the controller side, connect the shield to terminals 7
and 10.
On the side of the device, connect the shield to the
respective terminals.
Do not connect it to the cabinet ground or any other
ground points.
Connecting to External Systems or Interfaces

Connecting HMIs or Laptops

HMIs (e.g., the CLMMI00N22 or the CLMMI00N31) can be
connected via the HMI interface of the CLLIONLC01.
Laptops can be connected via the HMI interface or via the
L
W
interface of the CLLIONLC01.
ON
ORKS
Connecting the CLMMI00N22 Operator Interface
Connect the CLMMI00N22 Operator Interface to the HMI
interface of the CLLIONLC01 by means of
– the XW882 cable or
– the XW582 cable connected with an XW586 cable.
For mounting details refer to the CLMMI00N22 Installation
Instructions (Product Literature no.: EN2B-0126GE51).
For cable details refer to section "Preconfigured Connection
Cables" on page 10.
Connecting the CLMMI00N31 Operator Interface
Connect the CLMMI00N31 Operator Interface to the HMI
interface of the CLLIONLC01 Controller Module by
means of
– the XW882 cable or
– the XW586 cable connected with an XW585 cable.
For cable details refer to section "Preconfigured Connection
Cables" on page 10.
Connecting Laptops (XL-Online/CARE)
Connect a laptop (on which, e.g., XL-Online or CARE has
been installed) to the HMI interface of the CLLIONLC01
by means of
– the XW885 cable or
– the XW585 cable connected with an XW586 Cable.
For cable details refer to section "Preconfigured Connection
Cables" on page 10.

Connecting Modems

A LION System can be connected to a modem or an ISDN
terminal adapter via the Modem Interface of the
CLLIONLC01 by means of the XW586 Cable.
Connect the RJ45 female connector of the XW586 cable
to the modem interface of the CLLIONLC01 Controller.
Connect the 9-pin sub-D connector to the modem.
For cable details refer to section "Preconfigured Connection
Cables" on page 10.
Refer to Appendix 2 for details regarding remote
communication.
31
EN1Z-0921GE51 R0315

Advertisement

Table of Contents
loading

Table of Contents