Honeywell Centraline LION Installation & Commissioning Instructions page 5

Table of Contents

Advertisement

LION System
I/O Module Overview
Panel Bus
L
W
ON
ORKS
module
Bus module
CLIOP821A
CLIOL821A
CLIOP822A
CLIOL822A
CLIOPR822A CLIOLR822A
CLIOP823A
CLIOL823A
CLIOP824A
CLIOL824A
CLIOPR824A CLIOLR824A
CLIOPR825A –
CLIOP830A
--
CLIOP831A
--
1)
In addition to the power LED and service LED
2)
Changeover outputs
Table 3
Overview of I/O modules
Manual Overrides as per EN ISO 16484-2:2004
The manual override switches and potentiometers of the output modules (...R822A, ...R824A, and CLIOPR825A) support direct
operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units."
Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the
LION Controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the cor-
responding output LED will blink continuously, and the output module will send a feedback signal with the status "manual
override" and the given override position to the LION Controller (which will then also store this information in its alarm memory).
NOTE:
When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.
Corresponding Terminal Sockets
I/O module
Socket
CLIOP/CLIOL...
...821
XS821-22
XSU821-22
...822
XS823
...823
XSU823
...824
XS824-25
XSU824-25
...825
Table 4
Pluggable I/O modules and corresponding
terminal sockets
Description
Inputs Outputs
Analog input module
Analog output module
Analog output module
Binary input module
Relay output module
Relay output module
Floating output module
Mixed I/O module
Mixed I/O module
Scope of delivery
1 terminal socket,
1 bridge connector
1 swivel label holder
1 terminal socket,
1 bridge connector
1 swivel label holder
1 terminal socket,
1 bridge connector
1 swivel label holder
1 cross connector
5
Manual controls
8
8
8
8 Manual overrides 8 status LEDs
12
2)
6
2)
6
6 Manual overrides 6 status LEDs
3
3 Manual overrides 3 pairs of status LEDs
20
14
--
20
14
--
NOTE:
In the following, e.g., ...822 is used to summarize
all analog output modules (Panel Bus/L
Bus, with/without manual overrides).
System Overview
1)
LEDs
8 status LEDs
12 status LEDs
6 status LEDs
18 status LEDs
18 status LEDs
W
ON
ORKS
EN1Z-0921GE51 R0315

Advertisement

Table of Contents
loading