Troubleshooting; Testing Wiring Connections; Troubleshooting On The Cllionlc01 Controller - Honeywell Centraline LION Installation & Commissioning Instructions

Table of Contents

Advertisement

LION System

Troubleshooting

Testing Wiring Connections

Push-in terminals feature small holes (1 mm in diameter)
which can be used to measure the signals.
Insert a probe (1) as shown on the right.

Troubleshooting on the CLLIONLC01 Controller

The following LEDs of the CLLIONLC01 Controller can be used for troubleshooting purposes:
Power LED (green)
Alarm LED (red)
L
W
service LED
ON
ORKS
C-Bus Tx and Rx LEDs
HMI Tx and Rx LEDs
Modem Interface Tx and Rx LEDs
Power LED (green)
case
Power LED
1
ON
2
Flashing
3
Goes out briefly
Table 42 CLLIONLC01 power LED
Meaning
Normal operation
One or more of the internal voltage supplies
are outside of the permissible ranges. The
controller stops operation.
 The operator has activated the reset button
 The controller is performing a warm start
39
Fig. 56
Testing wiring connections
Remedy
No action necessary
Check power
Check wiring
If the problem persists, replace
hardware
No action necessary
Troubleshooting
EN1Z-0921GE51 R0315