11.7 Capturing the online values of a DB to reset the start values

11.7
Capturing the online values of a DB to reset the start values
You can capture the current values being monitored in an online CPU to become the start
values for a global DB.
● You must have an online connection to the CPU.
● The CPU must be in RUN mode.
● You must have opened the DB in STEP 7.
1. In the DB editor, click the "Monitor all tags" button. The "Monitor value" column displays
2. Click the "Show a snapshot of the monitored values" button to display the current values
3. Click the "Monitor all" button to stop monitoring the data in the CPU.
4. Copy a value in the "Snapshot" column for a tag.
5. Paste the copied value into the corresponding "Start value" column for the tag. (Right-
6. Save the project to configure the copied values as the new start values for the DB.
7. Compile and download the DB to the CPU. The DB uses the new start values after the
Note
The values that are shown in the "Monitor value" column are always copied from the
CPU. STEP 7 does not check whether all values come from the same scan cycle of the
CPU.
224
Use the "Show a snapshot of the monitored values" button to capture the current
values of the selected tags in the DB. You can then copy these values into the "Start
value" column of the DB.
the current data values.
in the "Snapshot" column.
– Select a value to be copied.
– Right-click the selected value to display the context menu.
– Select the "Copy" command.
click the cell and select "Paste" from the context menu.)
CPU goes to RUN mode.