Output (Aq) Measurement Ranges For Voltage And Current - Siemens SIMATIC S7-1200 Manual

Easy book
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

A.6.6

Output (AQ) measurement ranges for voltage and current

Table A- 40
Analog output representation for current
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
In an overflow or underflow condition, analog outputs will behave according to the device configuration properties set for
1
the analog signal module. In the "Reaction to CPU STOP" parameter, select either: Use substitute value or Keep last
value.
Table A- 41
Analog output representation for voltage
System
Decimal
Hexadecimal
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
AF00
-27648
9400
-27649
93FF
-32512
8100
-32513
80FF
-32768
8000
In an overflow or underflow condition, analog outputs will behave according to the device configuration properties set for
1
the analog signal module. In the "Reaction to CPU STOP" parameter, select either: Use substitute value or Keep last
value.
Easy Book
Manual, 11/2011, A5E02486774-04
0 mA to 20 mA
See note 1
See note 1
23.52 mA
20 mA
15 mA
723.4 nA
0 mA
± 10 V
See note 1
See note 1
11.76 V
10 V
7.5 V
361.7 μ V
0 V
-361.7 μ V
-7.5 V
-10 V
-11.76 V
See note 1
See note 1
A.6 Specifications for the analog I/O
Current Output Range
Overflow
Overshoot range
Rated range
Voltage Output Range
Overflow
Overshoot range
Rated range
Undershoot range
Underflow
Technical specifications
261