Siemens SIMATIC S7-1200 Manual page 269

Easy book
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Temperature
RTD type
coefficient
Pt 1000
Pt 0.003902
Pt 100
Pt 0.003916
Pt 200
Pt 0.003920
Pt 500
Pt 1000
Pt 0.003910
Pt 10
Pt 50
Pt 100
Pt 500
Ni 0.006720
Ni 100
Ni 0.006180
Ni 120
Ni 200
Ni 500
Ni 1000
LG-Ni 0.005000
LG-Ni 1000
Ni 0.006170
Ni 100
Cu 0.004270
Cu 10
Cu 0.004260
Cu 10
Cu 50
Cu 100
Cu 0.004280
Cu 10
Cu 50
Cu 100
RTD values below the under-range minimum value are reported as -32768.
1
RTD values above the over-range minimum value are reported as -32768.
2
Table A- 52
Resistance
Range
Under range
minimum
150 Ω
n/a
300 Ω
n/a
600 Ω
n/a
RTD values above the over-range minimum value are reported as -32768.
1
Easy Book
Manual, 11/2011, A5E02486774-04
Under range
Nominal
minimum
1
low limit
-243.0°C
-200.0°C
-243.0°C
-200.0°C
-273.2°C
-240.0°C
-273.2°C
-240.0°C
-105.0°C
-60.0°C
-105.0°C
-60.0°C
-105.0°C
-60.0°C
-240.0°C
-200.0°C
-60.0°C
-50.0°C
-60.0°C
-50.0°C
-240.0°C
-200.0°C
-240.0°C
-200.0°C
Nominal range
Nominal range
low limit
high limit
0 (0 Ω)
27648 (150 Ω)
0 (0 Ω)
27648 (300 Ω)
0 (0 Ω)
27648 (600 Ω)
A.7 RTD and Thermocouple modules
Nominal
range
range
high limit
850.0°C
850.0°C
1100.0°C
1100.0°C
250.0°C
250.0°C
180.0°C
260.0°C
200.0°C
200.0°C
200.0°C
200.0°C
Over range
maximum
1
176.383 Ω
352.767 Ω
705.534 Ω
Technical specifications
Over range
Normal
maximum
range
2
accuracy @
25°C
1000.0°C
± 0.5°C
1000.0°C
± 0.5°C
1295°C
±1.0°C
1295°C
±0.8°C
295.0°C
±0.5°C
295.0°C
±0.5°C
212.4°C
±0.5°C
312.0°C
±1.0°C
240.0°C
±1.0°C
240.0°C
±0.6°C
240.0°C
±1.0°C
240.0°C
±0.7°C
Normal range
accuracy
@ 25°C
±0.05%
±0.1%
±0.05%
±0.1%
±0.05%
±0.1%
Normal
range
accuracy
0°C to 55°C
±1.0°C
±1.0°C
±2.0°C
±1.6°C
±1.0°C
±1.0°C
±1.0°C
±2.0°C
±2.0°C
±1.2°C
±2.0°C
±1.4°C
Normal range
accuracy
0°C to 55°C
269