Technical specifications
A.1 General Technical Specifications
Electromagnetic compatibility
Electromagnetic Compatibility (EMC) is the ability of an electrical device to operate as
intended in an electromagnetic environment and to operate without emitting levels of
electromagnetic interference (EMI) that may disturb other electrical devices in the vicinity.
Table A- 2
Immunity per EN 61000-6-2
Electromagnetic compatibility - Immunity per EN 61000-6-2
EN 61000-4-2
Electrostatic discharge
EN 61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity test
EN 61000-4-4
Fast transient bursts
EN 6100-4-5
Surge immunity
EN 61000-4-6
Conducted disturbances
EN 61000-4-11
Voltage dips
Table A- 3
Conducted and radiated emissions per EN 61000-6-4
Electromagnetic compatibility - Conducted and radiated emissions per EN 61000-6-4
Conducted Emissions
EN 55011, Class A, Group 1
Radiated Emissions
EN 55011, Class A, Group 1
Environmental conditions
Table A- 4
Transport and storage
Environmental conditions - Transport and storage
EN 60068-2-2, Test Bb, Dry heat and
EN 60068-2-1, Test Ab, Cold
EN 60068-2-30, Test Db, Damp heat
EN 60068-2-14, Test Na, temperature shock
EN 60068-2-32, Free fall
Atmospheric pressure
236
8 kV air discharge to all surfaces
6 kV contact discharge to exposed conductive surfaces
80 to 1000 MHz, 10 V/m, 80% AM at 1 kHz
1.4 to 2.0 GHz, 3 V/m, 80% AM at 1 kHz
2.0 to 2.7 GHz, 1 V/m, 80% AM at 1 kHz
2 kV, 5 kHz with coupling network to AC and DC system power
2 kV, 5 kHz with coupling clamp to I/O
AC systems - 2 kV common mode, 1kV differential mode
DC systems - 2 kV common mode, 1kV differential mode
For DC systems (I/O signals, DC power systems) external protection is
required.
150 kHz to 80 MHz, 10 V RMS, 80% AM at 1kHz
AC systems
0% for 1 cycle, 40% for 12 cycles and 70% for 30 cycles at 60 Hz
0.15 MHz to 0.5 MHz
0.5 MHz to 5 MHz
5 MHz to 30 MHz
30 MHz to 230 MHz
230 MHz to 1 GHz
-40° C to +70° C
25° C to 55° C, 95% humidity
-40° C to +70° C, dwell time 3 hours, 5 cycles
0.3 m, 5 times, product packaging
1080 to 660h Pa (corresponding to an altitude of -1000 to 3500m)
<79dB (μV) quasi-peak; <66 dB (μV) average
<73dB (μV) quasi-peak; <60 dB (μV) average
<73dB (μV) quasi-peak; <60 dB (μV) average
<40dB (μV/m) quasi-peak; measured at 10m
<47dB (μV/m) quasi-peak; measured at 10m