System memory configures a byte with bits that turn on (value = 1) for a specific event.
Table 5- 2
System memory
7
6
5
4
Reserved
Value 0
Clock memory configures a byte that cycles the individual bits on and off at fixed intervals.
Each clock bit generates a square wave pulse on the corresponding M memory bit. These
bits can be used as control bits, especially when combined with edge instructions, to trigger
actions in the user code on a cyclic basis.
Table 5- 3
Clock memory
Bit number
Tag name
Period (s)
Frequency (Hz)
Because clock memory runs asynchronously to the CPU cycle, the status of the clock memory can change several times
during a long cycle.
Easy Book
Manual, 11/2011, A5E02486774-04
3
2
Always off
Always on
Value 0
Value 1
7
6
2.0
1.6
0.5
0.625
5.4 Configuring the operation of the CPU and modules
1
Diagnostic status
indicator
1: Change
0: No change
5
4
3
1.0
0.8
0.5
1
1.25
2
Easy to create the device configuration
0
First scan indicator
1: First scan after
startup
0: Not first scan
2
1
0.4
0.2
2.5
5
0
0.1
10