The following values were configured in the "Dynamics > General" configuration window: Acceleration = 10.0 and
Deceleration = 10.0
The axis is moved by an MC_MoveRelative task by the distance ("Distance") 1000.0. When the axis reaches the
target position, this is signaled via "Done_1". When "Done_1" = TRUE, another MC_MoveRelative task, with travel
distance 500.0, is started. Because of the response times (for example, cycle time of user program), the axis
comes to a standstill briefly (see zoomed-in detail). When the axis reaches the new target position, this is signaled
via "Done_2".
An active MC_MoveRelative task is aborted by another MC_MoveRelative task. The abort is signaled via
"Abort_1". The axis is then moved at the new velocity by the new distance ("Distance") 500.0. When the new target
position is reached, this is signaled via "Done_2".
Override response
The MC_MoveRelative task can be aborted
by the following motion control tasks:
 MC_Home Mode = 3
 MC_Halt
 MC_MoveAbsolute
 MC_MoveRelative
 MC_MoveVelocity
 MC_MoveJog
Easy Book
Manual, 11/2011, A5E02486774-04
Motion control is easy
10.7 MC_MoveRelative instruction
The new MC_MoveRelative task aborts the
following active motion control tasks:
 MC_Home Mode = 3
 MC_Halt
 MC_MoveAbsolute
 MC_MoveRelative
 MC_MoveVelocity
 MC_MoveJog