Fo Terminal Compartment: Open; Fo Cables: Connect - AUMA AUMATIC AC 01.2 Short Instructions

Profibus dp actuator controls
Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

2.2

FO terminal compartment: open

2.3

FO cables: connect

The AUMA plug/socket connector (SDE bus) is equipped with a connection board
for connecting the fibre optic cables. When removing the cover [1], the connection
board is easily accessible.
Figure 2:
AUMA plug/socket connector SDE bus
[1]
Cover (FO terminal compartment)
[2]
Screws for cover
[3]
O-ring
[4]
Cable entries for fibre optic cables
[5]
Blanking plugs
1.
Loosen screws [2] and remove cover [1].
2.
Insert cable glands suitable for FO cables.
The enclosure protection IP... stated on the name plate is only ensured if suita-
ble cable glands are used.
Example: Name plate for enclosure protection IP 68.
3.
Seal unused cable entries [4] with suitable blanking plugs [5].
4.
Insert the wires into the cable glands.
Figure 4:
Connection board with connector types SC (left), ST (right)
[1]
Channel 1
[2]
Channel 2 (for loop or line topology)
[3]
Protective cap/plug
TX
Optical output
RX
Optical input
FO connection
5

Advertisement

Table of Contents
loading