Corrective Action; Led Indications - AUMA AUMATIC AC 01.2 Short Instructions

Profibus dp actuator controls
Hide thumbs Also See for AUMATIC AC 01.2:
Table of Contents

Advertisement

Corrective action

4.
Corrective action
4.1

LED indications

12
Figure 11:
LEDs on connection board
[1]
Channel 1
[2]
Channel 2
LED
Designation
Colour
1
PWR
green
2
ERROR
red
3
STATUS
red
4
RX
green
5
Fail
red
6
Limit
yellow
7
Link/Act
green
8
Fail
red
9
Limit
yellow
10
Link/Act
green
Function
Device ready for operation (power supply available)
FO collective fault: Will be activated if either LED 5, 6 or LED 8
or 9 are illuminated or if the internal RS-485 connection is defec-
tive.
Byte with incorrect bit(s) received on RS-485
Byte received on RS-485
Optical receiving signal (channel 1) incorrect (no or insufficient
RX receive level). Both display and Profibus DP indicate: Wrn
FOC
Is illuminated with LED 7 (green):
System reserve (channel 1) reached (critical or permissible recei-
ve level).
The display shows the following indication: Diagnostic > FO cables
> FOC level channel 1 = Level critical, no Rx or Level critical, Rx
Furthermore, both the AUMATIC display and Profibus DP indicate:
Wrn FO cable budget
Is illuminated and LED 6 (yellow) is not illuminated:
Good RX receive level (channel 1).
Is blinking: Data is being received on RX (channel 1).
The display shows the following indication: Diagnostic > FO cables
> FOC level channel 1 = Level good, no Rx or Level good, Rx
Optical receiving signal (channel 2) incorrect (no or insufficient
RX receive level). Both display and Profibus DP indicate: Wrn
FOC
Is illuminated with LED 10 (green):
System reserve (channel 2) reached (critical or permissible recei-
ve level).
The display shows the following indication: Diagnostic > FO cables
> FOC level channel 2 = Level critical, no Rx or Level critical, Rx
Furthermore, both the AUMATIC display and Profibus DP indicate:
Wrn FO cable budget
Is illuminated and LED 9 (yellow) is not illuminated:
Good RX receive level (channel 2).
Is blinking: Data is being received on RX (channel 2).
The display shows the following indication: Diagnostic > FO cables
> FOC level channel 2 = Level good, no Rx or Level good, Rx