Connecting
5.4 Installing the Sensor
1. Perform all required menu steps up until the point where you respond to the [Install
2. Make note of the Number Index. Check to ensure that you have a matched set of
Note
An index pin will be inserted into the track rail hole designated by the Number Index to
position one of the sensors (see
3. Place the track rail assembly on the top surface of the pipe at the location where you
4. Holding the mounting track assembly in place, loop one of the strap clamps under the
48
Complete] prompt.
sensors. They both should have the same serial number but marked with wither an "A" or
"B" (e.g. 100A and 100B).
①
To SITRANS F 1010 Transmitter
②
1012CNF Series Cable
③
1011NPS Series Sensor Upstream
④
Sensor Clamp
⑤
1011NPS Series Sensor Downstream
Figure 5-20
Reflect Mount with Model 1012TN Mounting Track (Side View)
have determined it would be mounted. Ensure that it is a smooth area without any raised
spots or seams.
pipe, pull it around and maintain tension while slipping a link over the tension screw hook.
Tighten the tension screw enough to hold the assembly on the pipe, but still allow
rotation. Repeat for the other mounting strap.
⑪
in figure below).
⑥
Mounting Strap Guide
⑦
1012TN Series Mounting Track
⑧
Ultrasonic Couplant
⑨
Flow direction
⑩
Pipe
⑪
REF Hole Index Pin
Operating Instructions, 02/2012, A5E03086487-05
FST020 IP65 NEMA 4X